SSB 6720818454 (2016/02) US
Commissioning (for single boiler application) | 37
Below is a list of parameters:
Number Description Unit Default Min Max Step
3 CH Setpoint °C / °F 176 °F 68 °F 194 °F 0.9 °F
19 Design Supply Temp °C / °F 176 °F 68 °F 194 °F 1.8 °F
21 Baseline Supply Temp °C / °F 104 °F 68 °F 194 °F 1.8 °F
48 DHW/Tank Setpoint °C / °F 120.2 °F 104 °F 140 °F 0.9 °F
64 Preheat Mode - Comfort Eco Comfort -
72 Permit emergency mode - Yes No Yes -
Tab. 14 Level 1 parameters
Number Description Unit Default Min Max Step
1 Central Heating (CH) Mode - 1 0 5 1
2 Pump Mode - 0 0 4 1
4 System Pump Overrun Seconds 300 0 900 10
5 Boiler Pump Overrun Seconds 300 0 900 10
7 CH Hysteresis °C / °F 5.4 °F 0 36 °F 0.9° F
9 Anti Cycle Period Seconds 180 10 900 10
10 Anti Cycle Temp Diff °C / °F 12.6 °F 0°F 36 °F 0.9° F
11 Ramp Delay Step Mod. On / Off Disabled
14 Max Power CH % 100 50 100 1
15 Min Power CH/DHW % 1 1 30 1
20 Design Outdoor Temp °C / °F 24.8 °F -13 °F 77 °F 1.8 °F
22 Baseline Outdoor Temp °C / °F 69.8 °F 35.6 °F 86 °F 1.8 °F
23 Design Supply Min Limit °C / °F 68 °F 39.2 °F 179.6 °F 1.8 °F
24 Design Supply Max Limit °C / °F 194 °F 80.6 °F 194 °F 1.8 °F
25 Warm Weather Shutdn °C / °F 69.8 °F 35.6 °F 95 °F 1.8 °F
26 Boost Temp Increment °C / °F 0 °F 0 °F 54 °F 0.9 °F
27 Boost Time Delay Minutes 20 1 120 1
28 Night Setback Temp. °C / °F 18 °F 0 °F 90 °F 0.9 °F
29 Weather Setpoint °C / °F 68 °F 32 °F 122 °F 0.9 °F
35 DHW Mode - 0 0 2 1
36 DHW Tank Hyst. Down °C / °F 7.2 °F 0 °F 36 °F 0.9 °F
37 DHW Tank Hyt. Up °C / °F 0 °F 0 °F 36 °F 1.8 °F
38 DHW Tank Supply Extra °C / °F 54 °F 0 °F 54 °F 0.9 °F
42 DHW Priority - 0 0 2 1
43 DHW Max Priority Time Minutes 30 1 255 1
44 DHW Pump Overrun Seconds 15 0 255 1
73 Boiler Address - 0 0 16 1
74 Emergency Setpoint °C / °F 113 °F 68 °F 149 °F 0.9 °F
75 Delay Per Start Next Dep. Seconds 15 5 300 5
76 Delay Per Stop Next Dep. Seconds 15 5 300 5
77 Hyst Down Start Boiler °C / °F 9 °F 0 °F 36 °F 0.9 °F
78 Hyst Up Stop Boiler °C / °F 3.6 °F 0 °F 36 °F 0.9 °F
79 Max Setp Offset Down °C / °F 7.2 °F 0 °F 36 °F 0.9 °F
80 Max Setp Offset Up °C / °F 18 °F 0 °F 36 °F 0.9 °F
81 Start Mod Delay Fact Minutes 5 0 60 1
82 Next Boiler Start Rate % 80 10 100 1
83 Next Boiler Stop Rate % 30 10 100 1
84 Boiler Rotation Interval Days 1 0 30 1
85 DHW Boiler Assign - 0 0 16 1
89 Frost Protection Off / On Disabled Disabled Enabled -
90 Frost Protection Setpoint °C / °F 50 °F 33.8 °F 68 °F 0.9 °F
91 DHW Max Limit °C / °F 140 °F 104 °F 158 °F 0.9 °F
92 Fan Speed Maximum RPM * * * 60
Tab. 15 Level 2 parameters
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus SSB399 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus SSB399 in the language / languages: English as an attachment in your email.

The manual is 9,92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus SSB399

Buderus SSB399 Installation Guide - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info