Installation | 19
4.4.6 Condensate removal
The condensate water produced by the boiler during its normal operation
is collected by two plastic pipes (A and B) provided with the boiler and
connected with a plastic collector inside the case. A third tube (C) collects
the condensate output from the collector [Arrow is the direction of ow of
condensate].
Fig. 15
DANGER: The condensate pipe A and B, shown in Fig. 15,
must be lled with water or combustion gases will enter the
room with a risk of an excessive level of carbon monoxide.
To ll the condensate discharge add water from the vent (1) until you see
water come out of the condensate discharge pipe (2).
Fig. 16
The condensate water shall be discharged at atmospheric pressure,
i.e. by dripping into a siphon-shaped container connected to the home
sewage system or suitable drain, and shall be neutralized prior to draining
per local codes.
The boiler is equipped with three holes (in the right, left and back side) to
carry the condensate out the condensate drain tube.
Install the condensate drain tube through the appropriate hole and be
sure to pitch away from the boiler.
Do not reduce the diameter of the condensate drain pipe down
stream.
Never use copper pipes or of other material not intended for the
specic purpose, because the action of condensate will cause a rapid
deterioration.
Check that the condensate drain pipe is adequately sloping towards
the discharge point avoiding high points, which can inhibit the ow of
condensate.
Install the condensate pipe in such a way so as to avoid the freezing
of the liquid.
NOTICE: Verify condensate disposal / neutralization is in
accordance with local, state and federal regulations.
A condensate removal pump is required if the boiler is below the drain.
When installing a condensate pump, select one approved for use with
condensing boilers and furnaces. The pump should have an overow
switch to prevent property damage from condensate leakage.
4.5 Electrical connection
4.5.1 Power supply cable connection
To connect the boiler to the electrical supply, as required by local, state
and federal codes, provide and install a service switch (15 amp is
recommended).
The power supply cable can be inserted into the boiler using one of the
six knock out holes (A) on the sides as shown in Fig. 17.
WARNING: All the electrical wiring must be secured by
appropriate strain reliefs.
To secure the supply cable inside of the boiler use the cable clamp shown
in position B shown in Fig. 18.
Fig. 17
Fig. 18
A B C
H
2
O
1
H
2
O
2
A
B
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus SSB399 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus SSB399 in the language / languages: English as an attachment in your email.

The manual is 9,92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus SSB399

Buderus SSB399 Installation Guide - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info