Product description
Logano G515 – 6 720 647 208 (2014/09)6
2.1 Designated use
The Logano G515 oil/gas-fired boilers have been designed for the
heating of water.
The Logano G515 can be operated with oil, gas, and combination
burners. For a list of the approved burners, please contact Bosch
Thermotechnology Corp.
This boiler can be operated with an aquastat, the Logamatic 4000, and
other control systems.
2.2 Operating conditions
Thermostream technology is a unique feature of Buderus cast iron
boilers. Return water is preheated and mixed within the boiler before it
comes in contact with the heating surface of the combustion chamber.
The Thermostream technology ensures there is an even temperature
distribution in the boiler and avoids condensate forming within the
combustion chamber. This unique feature reduces thermal stress, the
main cause of failure of traditional cast iron boilers. The advantage of
this technology is the maintenance of the minimum operating
temperature of the boiler ( Tab. 3); this makes the installation of a
shunt pump unnecessary. This way, the costs for the pump itself and its
power consumption, as well as possible failure costs are saved. The
minimum boiler operating temperature as shown in the table below must
be reached within 10 minutes and then be maintained while the burner
is running.
This operating condition can be easily achieved by the controls
monitoring the boiler temperature and reducing the flow rate through
the boiler until the required temperature is reached. This is then
maintained by continuing to control flow based on the boiler water
temperature. The controls can reduce the flow rate by closing the valves
on the mixed heating circuits, modulating the boiler primary pumps or by
closing the motorized butterfly valves or by having a motorized valve in
the boiler return on a single boiler installation. The Buderus 4000 series
control panel can manage this process or it can be completed by the
BMS.
If it is not possible for the control panel to regulate the flow sufficiently to
meet this operating condition, then a shunt pump circuit must be fitted
to avoid the type of thermal stress that all boilers would experience in
these conditions. This shunt pump circuit can be controlled either with a
Buderus 4000 control panel or with a third-party controller. Failure to
ensure that the operating condition is maintained may lead to thermal
stress in the boiler and eventual failure of the sections which would be
outside the scope of the warranty.
2.3 Compliance with standards and regulations
Installation and operation of the system must comply with all applicable
codes, regulations and statutory requirements.
Installation, connection of the fuel supply and flue connector,
commissioning, connection of the electrical power supply, servicing and
repair may only be carried out by trained and certified heating
contractor. Only registered gas fitters may carry out work on the gas
train.
The system must be cleaned and serviced once a year. The operation of
the complete system must be tested at the same time. Any faults must be
corrected immediately.
The design and mode of operation of this boiler comply with the
American National Standard ANSI Z21.13/CSA4.9, latest edition for
Gas Fired Low Pressure Steam and Hot Water Boilers.
Other confirmed approvals and certifications are indicated by labels on
the boiler.
The heat exchanger has been designed and certified in accordance with
the ASME Boiler and Vessel Code, Section IV.
Control of all heating zones
with Buderus 4000
External controls (BMS)
or Aquastat control
Minimum flow rate none
Minimum return temperature °F ( °C) none
Minimum operating temperature oil boiler
1)
1) This temperature has to be reached within ten minutes of the burner starting and has to be maintained whilst the burner is firing.
°F ( °C) 122 (50)
Minimum operating temperature gas boiler
1)
°F ( °C) 122 (50) 140 (60)
Maximum supply temperature °F ( °C) 212
2)
/248
3)
(100
2)
/120
3)
)
2) The maximum supply temperature is 212 °F (100 °C), if the boiler is operated as hot water boiler.
3) The maximum supply temperature is 248 °F (120 °C), if the boiler is operated as a hot water generator.
Maximum operating pressure PSI (bar) 87 (6)
Time constant of the temperature controller sec 40
Time constant of the monitor/limiter sec 40
Table 3
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logano G515 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logano G515 in the language / languages: English as an attachment in your email.

The manual is 5,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logano G515

Buderus Logano G515 User Manual - English - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info