Inspection 12
45
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
12.3 Internal tightness testing
z Switch off the heating system using the main switch.
z Test the internal tightness of the gas burner fitting on
the inlet side, applying a test pressure of 7.7 inch
W.C. (20 mbar) in case of natural gas and 19.2 inch
W.C. (50 mbar) in case of LPG.
After one minute the pressure must not have dropped by
more than 3.8 inch W.C. (10 mbar).
z If the pressure has dropped more, you must check
the tightness of all gaskets and joints upstream of the
gas burner fitting using a foaming agent. Repeat the
pressure test if no leaks are found. If the pressure
has again dropped by more than 3.8 inch W.C.
(10 mbar) per minute you will have to replace the gas
burner fitting.
12.4 Measuring the ionization current
See subsection 9.12 "Measuring the ionization current",
page 33
12.5 Measuring the inlet gas pressure
See subsection 9.7 "Inlet gas pressure", page 30
12.6 Checking and adjusting the gas/air
ratio
See subsection 9.8 "Checking and adjusting the gas/air
ratio", page 31
12.7 Carrying out a gas tightness test in
operating conditions
See subsection 9.9 "Carrying out a tightness test in
operating conditions", page 33
12.8 Measuring the carbon monoxide
content (CO)
See subsection 9.10 "Measuring the carbon monoxide
content (CO)", page 33
12.9 Carrying out a pressure test of the
heating system
See chapter 9 "Start-up procedure", page 27.
12.10 Checking the functioning and the
safety of the air intake and flue gas
conduit
See subsection 9.5 "Checking the combustion air/flue
gas connection", page 30.
12.11 Checking venting systems
Check air intake and flue gas for obstruction or damage.
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logamax plus GB142-30 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logamax plus GB142-30 in the language / languages: English as an attachment in your email.

The manual is 4,63 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logamax plus GB142-30

Buderus Logamax plus GB142-30 User Manual - German - 16 pages

Buderus Logamax plus GB142-30 User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info