Start-up procedure 9
33
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
9.9 Carrying out a tightness test in
operating conditions
z Check the tightness of all gaskets and joints in the
burner gas circuit while the burner is operational,
using a foaming agent.
9.10 Measuring the carbon monoxide
content (CO)
z Measure the carbon monoxide content on the flue
gas sampling point (fig. 32).
The CO values in an air-free condition must be below
400 ppm or 0.04 vol. %.
Values of 400 ppm and up indicate that the burner
adjustment may be wrong, the gas burner fitting or the
heat exchanger are dirty or that there may be burner
faults.
z You must establish and resolve the cause. The appli-
ance must be operational when you do this.
9.11 Function testing
z You must check the functioning and, if readjustment
is possible, the adjustment of all control, regulating
and safety devices when carrying out start-up tests,
annual inspections or maintenance as required.
z You must also test the gas and water tightness.
9.12 Measuring the ionization current
z Switch off the heating system using the main switch.
DANGER
Leaks may be caused to pipes and screw
connections during start-up activities if flam-
mable gas explodes.
Only use approved leak detection agents
for leak detection such as a soapy water
solution.
CAUTION
due to a short circuit.
Cover damageable parts before leak
testing.
Do not spray the leak testing agent onto
cables, plugs or electrical connection
lines. Do not allow it to drip onto them
either.
Fig. 32 Flue gas sampling point
33


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logamax plus GB142-30 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logamax plus GB142-30 in the language / languages: English as an attachment in your email.

The manual is 4,63 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logamax plus GB142-30

Buderus Logamax plus GB142-30 User Manual - German - 16 pages

Buderus Logamax plus GB142-30 User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info