TR 100
4 Mounting
Before mounting the regulator, the volt-
age supply (230 V, 50 Hz) to the heating
unit must be interrupted.
4.1 Selecting the mounting location
It is important for the regulation quality of
TR 100 to select a suitable mounting location.
The installation room must be suitable for the
temperature regulation of the complete heating
system. The radiators installed in those rooms
must not be equipped with thermostatic valves.
Instead, hand valves with pre-adjustment
should be installed so that the heating output of
the radiators in the installation room of TR 100
can be set to the lowest possible value.
For the mounting location, select an interior
wall if possible and take care that neither
draughts nor heat radiation (not from behind
the wall, either, e.g. through ducts or hollow
walls, etc.) can have effects on the regulator.
Adequate space must be provided above and
below the regulator so that the room air can
circulate unimpeded through the ventilation
openings (hatched area in illustration
).
If the above mentioned conditions cannot all
be met it is recommended to use the external
room temperature sensor RF 1 (accessory)
and to mount this on a more adequate loca-
tion.
When connecting the room temperature sen-
sor RF 1 the built-in sensor in the regulator is
automatically deactivated.
4.2 Mounting the regulator
Loosen the top
(a)
from the base
(b)
de-
press the fasteners on the sides
(b1)
oft the
base and pull off the top
(a)
(illustration ).
The base
(b)
can be mounted either
with two screws
(c)
to a standard flush
connection box
(d)
dia. 55 mm
or
with 4 dowels (6 mm) and tallow-drop
screws (dia. 3.5 mm) directly to the wall
(illustration );
Take care that the regulator is mounted in
the right position (the clip must be legible)!
Connect with the mains accordingly (see
chapter 5).
Fit the regulator top
(a)
.
4.3 Mounting the accessories
The accessories external room temperature
sensor RF 1 and remote control switch (if ex-
isting) must be mounted according to the reg-
ulations and the respective mounting instruc-
tions.
5 Mains Connection
The following conductor cross sections from
TR 100 to the heating unit must be used:
Considering the regulations, at least cables of
the construction type NYM must be used for
mains connection.
All 24 V cables (test current) must be laid sep-
arated from cables leading 230 V or 400 V so
that no inductive influencing can take place
(minimum distance100 mm).
In case that inductive external influences e.g.
from power current cables, contact wires,
transformer towers, radio and television sets,
amateur radio sets , microwave equipment, or
similar are to be expected the cables leading
test signals must be shielded.
The corresponding electrical connection plan
(illustration
to ) is to be followed :
5.1 Accessory mains connection
Connect the external room temperature sen-
sor RF 1 (if existing) as shown in
illustration
.
If required, the cables of RF 1 can be extend-
ed with a cable with twisted twin conductors.
This will make sure that the measured values
of the sensor will not be influenced.
Connect the remote control switch (if existing)
as shown in illustration For minimum re-
quirements see chapter 2.2 accessories.
When the switching contact of the remote con-
trol switch is deactivated the heating system
will switch to economical operating mode, “F”
is displayed. When the switching contact is
activated the mode of operation set at the reg-
ulator is also activated (illustration ).
4
5
6
Length up to 20 m 0.75 mm
2
up to 1.5 mm
2
Length up to 30 m 1.0 mm
2
up to 1.5 mm
2
Length over 30 m 1.5 mm
2
9 11
7
8
8
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch TR 100 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch TR 100 in the language / languages: English, Polish as an attachment in your email.

The manual is 1,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch TR 100

Bosch TR 100 Quick start guide - German - 1 pages

Bosch TR 100 Usermanual and installation guide - German - 30 pages

Bosch TR 100 User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info