780636
20
Zoom out
Zoom in
Previous page
1/24
Next page
Rego 1000 – 6 721 831 662 (2021/03) en
20
Alarm
7.9.2 Temporary heat pump stop E21.RLP
Function: Activated when the pressure in the refrigerant circuit of the
heat pump becomes too low. If the information appears several times
during a certain time period, the information transforms into a category
A alarm ( Chapter 7.7.2).
Reset condition: The pressure goes back to the permitted level.
Category: I.
7.9.3 Temporary heat pump stop E21.RHP
Function: Activated when the pressure in the refrigerant circuit
becomes too high. If the information appears several times during a
certain time period, the information transforms into a category A alarm
( Chapter 7.7.3).
Reset condition: The pressure goes back to the permitted level.
Category: I.
7.9.4 Low temperature collector circuit in E2x.T10
Function: The information is given if the temperature of the refrigerant
to the heat pump is too low. If the information appears several times
during a certain time period, the information transforms into a category
A alarm ( Chapter 7.7.5).
Reset condition: The temperature of the collector circuit exceeds the
lowest permitted temperature.
Category: J that can be transformed into A.
7.9.5 Low temperature collector circuit out E2x.T11
Function: The information is given if the temperature of the refrigerant
from the heat pump is too low. If the information appears several times
during a certain time period, the information transforms into a category
A alarm ( Chapter 7.7.6).
Reset condition: The temperature of the collector circuit exceeds the
lowest permitted temperature.
Category: J that can be transformed into A.
7.9.6 Hot water peak failure, new try within 24 hours
Function: The hot water has not come up at the right temperature. The
hot water peak is repeated at the same time on the next day.
Reset condition: The correct hot water peak temperature is reached.
Category: Z.
7.9.7 Temporary heat pump stop due to working area limits
Function: The compressor stops until the hot gas temperature falls
below the set limit. The warning can occur when the heat pump works
close to the lowest permitted outdoor temperature.
Reset condition: The hot gas temperature is within the range of the
compressor.
Category: Z.
7.9.8 Temporary hot water stop due to working area limits
Function: Ongoing hot water operation is aborted and replaced with
heating operation. The warning can occur when the heat pump works
close to the lowest permitted outdoor temperature.
Reset condition: The hot gas temperature is within the range of the
compressor.
Category: Z.
7.9.9 Additional heat is now working at its highest temperature
Function: The additional heat begins to be stepped down. The
information is activated in additional heat mode if the outgoing
temperature (T1 or T8) approaches the set maximum value. The
information is blocked during hot water peaks or extra hot water.
Reset condition: The information is deactivated when the temperature
falls.
Category: Z.
7.9.10 Temporary hot water stop E2x
Function: Ongoing DHW mode is temporarily interrupted; the system
changes over to heating mode.
Reset condition: DHW temperature drops a few degrees.
Category: Z.
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Rego 1000 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Rego 1000 in the language / languages: English as an attachment in your email.

The manual is 4.13 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info