Heatronic 40007738003455 (2014/04) 13 of 60
*Requires 500 Resistor in Parallel
CONVERSION TABLE 2 - 10
4 - 20 mA* 2 - 10 V (dc) Boiler Target
0 0 – – – (OFF)
4 2 50°F (10°C)
6 3 70°F (21°C)
8 4 90°F (32°C)
10 5 110°F (43°C)
12 6 130°F (54°C)
14 7 150°F (66°C)
16 8 170°F (77°C)
18 9 190°F (88°C)
20 10 210°F (99°C)
EMS Offset
For external input operation, the boiler target (determined
from the external input signal) may be fine tuned. The EMS
OFFST setting is used to provide the fine tuning. The setting
may be adjusted ±10°F (±5.5°C). When set to 0°F (0.0°C), if
the temperature determined from the external signal is 140°F
(60.0°C), the boiler target will be 140°F (60.0°C). When set
to +5°F (+3.0°C) & with the same external signal represents
140°F (60.0°C), the boiler target will be 145°F (63.0°C).
Example
Range = 0 - 10 V (dc)
Input = 7 V (dc) 157°F (69°C)
Offset = +5°F (3°C) + F (3°C)
Boiler Target = 162°F (72°C)
The minimum & maximum settings also apply for external input
operation. For example, if a boiler minimum of 140°F (60.0°C) is
set & the external signal received represents 80°F (27.0°C), the
boiler target will be 140°F (60.0°C). MIN will also be displayed
in the status field to indicate that a limiting condition is in effect.
This also applies for the MAX limit.
Indirect Domestic Hot Water (DHW) Operation
IDHW operation is applicable during the following application
modes: outdoor temperature reset, fixed setpoint & EMS.
DHW Call
-- - -- -- -- - -- -- -- -- - -- -- -- - - - -- -- -- - -- -- --
A DHW Call is required in order for the control to provide heat
to an indirect DHW tank. Once the control registers a DHW
Call, it will display the “DHW” icon under Calls in the display.
A DHW Call can be provided in three ways:
DHW Tank Aquastat
If a DHW Tank Aquastat (mechanical switch) is used to apply
a DHW Call, the tank is heated to the aquastat temperature
setting. A dry contact or 24 V (ac) signal is applied across the
DHW Tank Call terminals 7 & 8.
Requirements
: IDHW Sensor must be set to Off.
DHW Sensor
A DHW Tank Sensor provides superior temperature control of
the tank compared to an aquastat. The control can register a
DHW Call when a DHW Sensor is wired to terminals 21 & 22.
Once the DHW Sensor temperature drops 1/2 of the IDHW
Differential setting below the IDHW Setpoint, the control
registers a DHW Call.
Requirements: The IDHW Sensor must be set to On. There
cannot be an external IDHW Call when using a DHW sensor.
DHW Differential
---------------------------------
Due to large differences between the heating load & the DHW
load, a separate DHW differential should be used whenever a
DHW Call is present. This will improve staging & boiler cycling.
When using a DHW Sensor, a DHW Call is registered when the
temperature at the DHW sensor drops the IDHW DIFF setting
below the IDHW Setpoint setting. The DHW Call is satisfied
once the temperature at the DHW Sensor rises to the IDHW
Setpoint setting.
Boiler Target Temperature during a DHW Call
------
When a DHW Call is present, a boiler target is determined.
When using a DHW Tank Aquastat, the boiler target is set
to the IDHW Exchange setting.
When using a DHW Tank Sensor, the boiler target is fixed
at the IDHW Setpoint setting plus 40°F (22.0°C).
When using a tekmarNet
®
Setpoint Control, the boiler target
is set to the devices Exchange Supply setting.
If there are multiple devices calling for heat, the boiler target
is set to the highest temperature requirement.
IDHW During UnOccupied
-- - - - - - -- -- -- -- -- -- -- -- -
When using a DHW Tank Aquastat, a second IDHW Exchange
setting is available for the UnOccupied or Sleep period.
When using a DHW Sensor, a second IDHW Setpoint setting
is available for the UnOccupied or Sleep period.
DIP Switch must be set to Setback to view UnOccupied items.
During the Away Scene, DHW Calls are ignored.
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Heatronic 4000 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Heatronic 4000 in the language / languages: English as an attachment in your email.

The manual is 7,85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Heatronic 4000

Bosch Heatronic 4000 User Manual - French - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info