Installation
CP1 – 6 720 645 612 (2012/10)
14
Fig. 11 Wires in the fault indication system
[1] Brown wire
[2] Black wire
[3] Blue wire
[4] Fault indication cable
3.4 Making the electrical connection
The following must be observed for the electrical connection:
Make the electrical connection in accordance with the applicable
standards in the relevant country (Germany: VDE 0100).
Observe the connection diagrams of all connected appliances and
accessories.
Only use the electrical connection to the condensate pump to supply
power to the condensate pump.
Check whether the earth resistance is lower than 38 Ω.
Protect the condensate pump via an RCD with a rated response
current of not more than 30 mA.
The condensate pump power plug must be easily accessible.
B Plug the condensate pump into an earthed socket.
3.5 Checking the function
Operational description
The condensate pump contains a pump. The condensate pump tank is
equipped with a float switch that controls the pump operation. The
pump starts as soon as condensate enters the condensate pump.
The float switch turns the pump on and off.
If a fault indication system is connected:
The fault indication system is triggered if there is an unusually high
water level.
To protect the electronic switching components of the condensate
pump, the water, that continues to runs into the tank after the fault
indication has been triggered, is drained off via the overflow device in
the cover.
Checking the function of the pump and float switch
B Fill the condensate pump with water until the pump starts.
B Check whether water is pumped away when the pump is operational.
B Check whether the pump shuts down.
Checking the function of the fault indication system
B Fill with water until the fault indication is triggered.
B Check whether the fault indication system triggers the function of the
connected component (Æ chapter 3.3, page 13).
B Stop filling with water.
B Check whether water is pumped away when the pump is operational.
B Check whether the pump shuts down.
B Check whether the fault indication system reverts to standard
operation.
The condensate pump functions OK.
If a fault occurs
B Locate and remedy the fault.
3.6 Troubleshooting
DANGER: Risk to life from electric shock!
Never open the condensate pump as long as it is
connected to the mains.
B All electrical work must be carried out by an
electrician.
B Before starting electrical work, isolate all poles and
secure against unintentional reconnection.
Check the condensate pump for function at least once
per year.
What triggers the fault indication system varies
depending on the connection version installed
(Æ chapter 3.3, page 13).
6 720 645 612-09.2ITL
1
2
3
4
DANGER: Risk to life from electric shock!
Never open the condensate pump as long as it is
connected to the mains.
B All electrical work must be carried out by an
electrician.
B Before starting electrical work, isolate all poles and
secure against unintentional reconnection.
B Work on electrical components of the pump must only
be carried out by authorised customer service
personnel.
Fault
Possible
cause
Remedy
Condensate pump
does not start.
Plug is not plugged
in.
B Insert
the plug.
Power failure B Check mains power.
Floater is blocked. B Check water tank in
condensate
pump.
Condensate hose is
blocked.
B Clean inlet hose to
condensate pump.
Condensate pump
does not pump.
Check valve is
blocked.
B Clean valve.
Drain hose is
blocked.
B Clean drain hose.
Tab.3 Malfunctions
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch CP1 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch CP1 in the language / languages: English, German, Dutch, French, Italian, Polish, Portuguese, Turkish, Spanish as an attachment in your email.

The manual is 6,63 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info