Technical information
29
Compress 3400i AWS – 6721852066 (2023/01)
11.3.2 Bypass of the heating system
If the heating system is not able to permanently meet the minimum
volume and flow and if the pressure loss in the circuit is more than
allowed, a bypass should be installed according to the instructions.
Fig. 28 Indoor unit with heating circuit and bypass
[1] Bypass
[2] Flow pipe diameter
[3] Return pipe diameter
Fig. 29 Indoor unit with heating circuit and DHW heating
[1] Bypass
[2] Flow pipe diameter
[3] Return pipe diameter
Fig. 30 Bypass details (
[1] [CS3400iAWS 10 E fig. 28 and 29)
[L] Minimum bypass length
[D] Pipe diameter
The bypass must have an outer pipe diameter of 22 mm (Cu) and be
installed between the supply and return. The bypass must be installed
close to the indoor unit (CS3400iAWS 10 E), and no more than 1.5 m
away from it.
Table 12 Pipe diameter and bypass lengths
Fig. 31 Bypass
[A] Bypass, straight design
[B] Bypass, U-shaped design
T
T
0010036801-001
1
2
3
PC1
1
2
3
SC1
PC0
PC1
0010036802-001
Outdoor
unit
([2] and [3]
fig. 28
[CS3400iAW
S 10 E] and
29) external
flow/return
pipe diameter
([1] fig.
28 and 29)
external
bypass pipe
diameter ([D]
fig. 30)
Bypass design
([A] fig.
31)
([B] fig.
31)
Minimum
bypass
length ([L]
fig. 30)
Minimum
bypass
length ([L]
fig. 30)
mm mm mm mm
CS3400iA
WS 4-10
OR-S
22 22 200 100
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Compress 3400i AWS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Compress 3400i AWS in the language / languages: English as an attachment in your email.

The manual is 7.89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Compress 3400i AWS

Bosch Compress 3400i AWS User Manual - English - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info