12.3.4 Loop resistance and prospective fault current
ThedenitionofthenominalvoltageforcalculatingI
PFC
ismodiedasfollows:
- 55 V for selection of a single-phase center-tapped network,
- 63 V for selection of a three-phase network.
The test can be carried out for both combinations (L1-PE and L2-PE). For each individual test re-
sult, the corresponding indication is shown.
Nominal input voltages:
Nominal input voltage U
N
Voltage range
single-phase network, 55 V (44V≤U≤61V)
three-phase network, 63 V (56V≤U≤70V)
If the input voltage is outside this range, this is displayed on the online voltage / terminal monitor
together with the symbol.
12.4 Technical data
Here, only technical data are listed which differ from the data in chapter 9.
12.4.1 FI/RCD Testing
General data
Nominal fault current
10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA
Accuracy of the nominal fault current 0 / + 0.1 × I
; I
= I
∆N
. 2 × I
∆N
. 5 × I
∆N
- 0.1 I
/ + 0; I
= ½ × I
∆N
Maximum nominal differential current
forthespeciedaccuracy 1000mAfürI
∆N
500mAfür2× I
∆N
100mAfür5× I
∆N
Maximumtestingcurrent 1A(forZ-LOOP<1Ω)
Wave form of the testing current sine waves (AC), pulsating (A)
DC shift for pulsating testing current 6 mA (typical)
Type of FI/RCD standard (G, undelayed), selective (S, delayed)
Initial polarity of the testing current 0° or 180 °C
Nominal input voltage 55 V / 63 V (45 Hz ÷ 65 Hz)
Contact voltage
In compliance with EN61557-6, the measuring range for the limiting contact voltage of 25 V goes
from 3.0 V to 32.6 V.
In compliance with EN61557-6, the measuring range for the limiting contact voltage of 50 V goes
from 3.0 V to 66.0 V.
Measuring range (V) Resolution (V) Accuracy
0.0 - 9.9 0.1 (- 0 %/ + 15 % of reading + 2 digits)
10.0 - 99.9 0.1 (- 0 %/ + 15 % of reading)
Understandardconditions,theaccuracyshallapplyforoneyear.Thetemperaturecoefcientout-
side these limiting values is +1 digit.
Testing current max. 0.5 × I
∆N
76


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Benning IT 110 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Benning IT 110 in the language / languages: English as an attachment in your email.

The manual is 6,86 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Benning IT 110

Benning IT 110 User Manual - German - 83 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info