12
Bellfi res English
Installation instructions
Wall-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At walls in buildings with staggered Not permitted if A, B, or C are located
heights. above the outlet.
On a wall - general. (*) Above the outlet: >2 m
Below the outlet: >0.75 m
Left and right of the outlet: >0.75 m
At <1 m from the roof overhang. >2 m
Beneath balconies, walkways etc. >2 m from the underside of the
protruding balcony or walkway.
Beneath balconies, walkways >2 m
etc. where the outlet extends to
the front.
To the garden or on the terrace. >2 m to the outside space. (**)
With respect to a facing wall. >2 m (if the distance from the facing
wall is less, the criteria detailed for
“On a wall - general” apply).
Enquire at your local gas company for the regulations relating to outlets
positioned opposite each other and outlet(s) in facade(s) that form an angle.
(*) These minimum distances do not apply if there is an obstruction
between the outlet and A, B and C that protrudes at least 0.5 m from
the wall and has a length exceeding the distance.
(**) This distance is not required if the outlet is situated at least 1 m
higher than the intended area of the outside space.
If the outlet has a clearance of less than 0.5 m from the hard surface of a public area at
a height of less than 2 m, it must be fi tted with an effective protector. The mesh size of
the guard must not affect the correct operation of the appliance.