4.3 Clearances to the concentric flue pipe in a casing
Installation of the concentric flue in a casing of non-combustible material is possible.
Make sure that the casing material complies with the values in the table. Also make sure
that the casing is sufficiently ventilated according to the values in the table.
Concentric flue pipe safety distances when mounted in a non flammable casing:
Item Description
A Distance from bottom of concentric flue pipe to casing minimum 2.5 cm.
B Distance from top of concentric flue pipe to casing minimum 5.0 cm.
C Distance from side of concentric flue pipe to casing minimum 2.5 cm.
D Distance between two ventilation grilles maximum 3.0 m.
E Concentric flue pipe Ø60 / Ø100 mm.
FCasing made of a non flammable insulation plate/board with a thermal conductivity of
maximum 0.20 W/m.K. Thickness minimum 10.0 mm.
G Ventilation grille. Nett opening each grille minimum 150 cm2 .
H Wall/ceiling - flammable or non flammable.
Note: It is permitted to pour the non-combustible -water-tight- casing in
concrete or to brick it in, provided that the material of the casing is suitable for
this and has all the properties as stated in the table above. Furthermore, the
ventilation of the casing must remain guaranteed and that the pipes can still
be accessed for maintenance / replacement at all times.
Clearances
Opti-Vent 19
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Barbas Opti-Vent-systeem at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Barbas Opti-Vent-systeem in the language / languages: English as an attachment in your email.

The manual is 7.95 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Barbas Opti-Vent-systeem

Barbas Opti-Vent-systeem User Manual - German - 52 pages

Barbas Opti-Vent-systeem User Manual - Dutch - 52 pages

Barbas Opti-Vent-systeem User Manual - French - 52 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info