Minimum separation distances for roof and wall outlet(terminal) in mm
Location
Minimum
distance
[mm]
A Below an opening 2 on the same wall/roof 2000
B Above an opening 3 on the same wall/roof 700
C Horizontally to an opening 3 on the same wall/roof 700
D Horizontally to a facing opening 3 in a opposite wall 2000
E From a roof terminal under an opening 3 in a nearby rising wall 4000
F Above a flat or pitched roof 300
G Horizontally from a terminal on the same roof 300
H From a structure (e.g. brick chimney) on the roof 300
I Below a roof window in a pitched roof 2000
J Above a roof window in a pitched roof 600
K Horizontally to a roof window in a pitched roof 600
L From an internal or external corner 500
M From a vertical drainpipe or soil pipe 300
NBelow gutters, soil pipes or drainpipes, made of flammable materials 500
Below gutters, soil pipes or drainpipes, made of non-flammable materials 300
OBelow eaves, made of flammable material 500
Below eaves, made of non-flammable material 300
P Below balcony 3 or car port roof 2000
Q Beyond the balcony 4 edge 0
R On either side of a balcony 41500
S Above ground, roof or balcony 4 level 300
T From a surface facing the terminal 500
U From a terminal facing the terminal (at the same height) 600
V From an opening in the car port into the building 1200
W Vertically from a terminal on the same wall 1200
X Horizontally from a terminal on the same wall 300
Y From a boundary alongside the terminal 1000
Z From a boundary facing the terminal 2000
If the outlet is installed less than 0.5 m horizontally and less than 2 m vertically from a
public area, install an effective protector.
Make sure that the mesh size of the guard does not effect the operation of the
appliance.
If the height of the outlet is less than 3 meter from the floor, the distance between the
outlet and a garden or a terrace must be minimum 2 meter.
2An opening here means an element that is permanent open (example: an air vent) or that can open
(example: a door or window). But, in addition, the distance between outlet and built-in elements
(example: window, door) must be minimum 300 mm.
3Balcony or gallery of an apartment building.
Requirements
Gas Fire Front 90-75 11
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Barbas Gas Fire Front 90-75 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Barbas Gas Fire Front 90-75 in the language / languages: English as an attachment in your email.

The manual is 9 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Barbas Gas Fire Front 90-75

Barbas Gas Fire Front 90-75 Installation Guide - English - 96 pages

Barbas Gas Fire Front 90-75 User Manual - English - 36 pages

Barbas Gas Fire Front 90-75 Additional guide - German - 104 pages

Barbas Gas Fire Front 90-75 Installation Guide - German - 104 pages

Barbas Gas Fire Front 90-75 User Manual - German - 44 pages

Barbas Gas Fire Front 90-75 Additional guide - Dutch - 104 pages

Barbas Gas Fire Front 90-75 Installation Guide - Dutch - 100 pages

Barbas Gas Fire Front 90-75 User Manual - Dutch - 40 pages

Barbas Gas Fire Front 90-75 Additional guide - French - 104 pages

Barbas Gas Fire Front 90-75 Installation Guide - French - 100 pages

Barbas Gas Fire Front 90-75 User Manual - French - 40 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info