Operating manual Fireplace inserts slied flat + II EN 7 | Requirements at the installation location
53
7 Requirements at the installation location
7.1 Requirements at the room of installation
Fireplaces must not be set up in:
spaces in which the required combustion air supply is not guaranteed.
spaces which are generally accessible, especially emergency exits staircases in residential building
with no more than 2 apartments are not included in general accessible spaces.
spaces in which easily flammable or potentially explosive substances or mixtures are processed,
stored or manufactured.
spaces, apartments or units from which air is extracted with the aid of ventilators, such as ventila-
tion- or hot-air heating installations, extractor hoods or exhaust air tumble dryers. Unless the safe
function of the fireplace insert is ensured:
This is ensured if:
the systems only circulate air within a space.
the systems have safety features which autonomously and reliably prevent negative pressure in
the installation space.
simultaneous operation of the fireplace and the air-extracting system is prevented by safety
features.
the flue gas routing is monitored by a particular piece of safety equipment.
no negative pressure greater than 0.04 mbar occurs overall via the combustion air flow of the
fireplace insert and the volume flows of the ventilation systems in the installation room and
rooms connected via the ventilation network. This must also be guaranteed when easily access-
ible ventilation system control equipment is adjusted or removed.
TIP
When operating a controlled living room ventilation system, the use of a DIBT-tested heat-producing
appliance connected to a balanced flue is recommended.
7.2 Installing the fireplace insert
Observe the guidelines on fire safety, such as thermal insulation and air grille sizes.
DANGER
Fire hazard
Operating your Austroflamm fireplace insert with too high a fuel feed will create a risk of the chimney
and adjacent components or furniture overheating.
7.3 Combustion air supply
For heat-producing appliances that draw their combustion air from the installation room an adequate
supply of combustion air into the room must be provided. Other heat-producing appliances or ventila-
tion facilities in the installation room or combustion air network may make a separate combustion air
supply from outside necessary.
Air suction systems (e.g. ventilation system, cooker hood, etc.) that are operated together with the
heat-producing appliance in the same room air network may disrupt the combustion air supply and
possibly require additional safety measures under the heating regulations.
53


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II in the language / languages: English as an attachment in your email.

The manual is 14.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II

Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II User Manual - German - 124 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info