16
17
Sanitary hot water mixture valve
Safety valve kit
Ball valve
15
TW
TC
TR
Tuo
Hot water temperature
Cooling or heating water temperature
Room temperature
Monoblock unit outlet water temperature
Tv2
Monoblock unit return water temperature
Monoblock unit coil temperature
Temperature of water after mixture valve 1
Temperature of water after mixture valve 2
Tv1
Tup
Tui
1
2
3
4
5
6
Monoblock unit
Indoor control unit
Buffer tank
Sanitary hot water storage tank
Motorized 3-way valve
Mixture valve 1 (0~10V)
8
9
10
11
12
Circulation pump
Sanitary hot water circulation pump(if need)
Circulation pump for distribution system 1
Circulation pump for distribution system 2
AH-Auxilary heater inside unit
HBH-Heating Back-up Heater
HWTBH-Hot Water Tank Back-up Heater
13
14
Item Name
7Mixture valve 2 (0~10V)
19
20
Pressure meter
Motorized 2-way valve
Filter
18
21 One-way valve
Item Name
M1
M2
Drainage
High temperature
hot water export
HWT
City water
M
T/P
valve
T/P
valve
17
21
18
20
7
16
BFT
FLH1
FLH2
FLH3
3. Installation
3.1.2 Heater /cooling distribution system
Note:
Buffer tank is always recommended to be included in the system , especially when the distribution system has
water volume less then 20L/W. It should be installed between heat pump and distribution system , in order to:
1) Ensure heat pump unit has stable and enough water flow rate.
2) Store heat to minimize fluctuation of system heating/cooling load.
3) Extend the water volume of distribution system for proper working of heat pump unit.
If distribution system has enough water volume and can ensure the water flow rate of heat pump system , buffer
tank can be excluded in the system . But in this way , please move temperature sensor Tc (Cooling/heating
temperature sensor ) to water return pipe to minimize the fluctuation of water temperature caused by compressor
speed changes.
46
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATTACK Inverter R32 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATTACK Inverter R32 in the language / languages: English as an attachment in your email.

The manual is 51.37 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info