Errors, functions and actions of the regulator – summary
Errors and functions Actions or operation of the regulator
Power shortage After the power supply is restored, the operation state is reset as it
was before the power shortage (the boiler is started or stopped
again).
Too high boiler temperature < 90 °C: the fan is stopped
> 89 °C: the fan is started
Incorrectly measured values of
the boiler temperature
The flue gas fan and the supply pump are stopped. The boiler cannot
be started.
Incorrectly measured values of
flue gas
The boiler can be started. The regulator works with the alternative air
V1 and V2. It is necessary to turn the boiler off manually after
burning down!
Incorrectly measured values of
O
2
sensor (Lambda probe)
No line plot is displayed during the heating up.
It is possible to start the boiler, the regulator works with the
alternative air V1 and V2.
Automatic stop functionby the
flue gas sensor
If the boiler works for
30 min
utes and the flue gas temperature
decreases by 25 % during 15 minutes, the boiler is stopped.
The STB is started The surplus heat outtake is stopped
if the boiler temperature is
< 85 °C. Then, if the boiler temperature increases> 86 °C, the surplus
heat outtake.
Function of the switch contact When the boiler is in operation
: WK/AK
is closed
When the boiler is turned off and the flue gas temperature is<100 °C:
WK/RK is closed
The CPU error All the relays are tu
r
ned off by the
Hardware Watchdog
Protection against freezing By the boiler stopped with the temperature< 7 °C:
Start of the supply pump, Y1 and Y2 = 100 %.
If the boiler temperature increases to > 8 °C, the supply pump is
stopped.
Y1=0 %, Y2= 100 %.
Protection of the flue gas fan and
the flue gas sensor against
overheating
Flue gas temperature
> 350
°C, the flue gas fan is turned off
Flue gas temperature< 299 °C, the flue gas fan is turned on
Short circuit of the„+“ button Button of the regulator does not react even to a significant pressure
Function of access (Menu) The menu automatically disappears after the safety time elapses
Safety test Takes max. 30 min and it is automatically terminated or interrupted,
if the boiler temperature is> 110 °C,or the„+“button has not been
pressed for 30 seconds
Operating range of the
automatic adjustment of the
return connection to the
particular value.
Between 60 °C and 80 °C
Operation without settings is
controlled by technician
The regulator is adjusted after the setting by producer.
Data storing Only when there is enough energy> 160V.
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATTACK DPX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATTACK DPX in the language / languages: English as an attachment in your email.

The manual is 11.03 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of ATTACK DPX

ATTACK DPX Additional guide - English - 21 pages

ATTACK DPX Additional guide - German - 21 pages

ATTACK DPX User Manual - German - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info