INFORMATION menu
• Photocell – Displays the current value that the photocell sees.
• Temperature TS – displays the current TS temperature - (exhaust temperature (S15 = 1) or
lower temperature (S15 = 2))
• Temperature TV – displays the current TV temperature - (water temperature (S15 = 1) or upper
temperature (S15 = 2))
• Temperature TK – displays the current TK temperature - (boiler temperature ( S15 = 1, S15 = 2,
S15 = 4, S6 = 12, S6 = 13, S14 = 12, S14 = 13), central tank temperature (S15 = 3, S6 = 14,
S14 = 14 ), central tank temperature as a second deactivation sensor for burner TS2 (S26 = 0))
• Temperature TSV – displays the current TSV temperature - (exhaust temperature (S15 = 1,
S15 = 2, S15 = 4, S34 = 1, S34 = 2), solar collector temperature (S15 = 3, S6 = 14, S14 = 14))
Short explanation:
This always depends on whether the burner regulation function based on two temperatures on the
accumulation tank is on or off, and whether the automatic start function after wood burns out is
activated.
The default settings are S15 = 1 and S34 = 0, which means that the function for controlling the
burner by two sensors is deactivated and the AUTOSTART function for DCxxSP(X)/(EP), CxxSP,
KCxxSP burns is also off. The burner is only controlled by thermoregulators on the boiler panel.
The customer may connect the exhaust temperature sensors TS and TSV and the water temperature
sensors TV and TK to the burner so that they only serve as information.
If we set S15 = 2, the function for regulation by two temperatures on the tank is activated and
so we connect the water tempearture sensor in the lower part of the tank TS and the water
temperature sensor in the upper part of the tank TV to the clamps of the burner connector.
If we set S15 = 3, the function for regulation by two temperatures on the tank is also activated,
simultaneously with the solar functions. It is thus also necessary to connect the TK sensor
located in the middle of the accumulation tank between the TV and TS sensors and the TSV
solar collector sensor.
If we are going to use the AUTOSTART function for boilers DCxxSP(X)/(EP), CxxSP, KCxxSP
(S34 = 1 or S34 = 2), we must also connect the TK sensor as a boiler sensor and the TSV sensor
as the exhaust temperature sensor.
If we are going to control the pump in the boiler circuit (recommended S14 = 12 or S14 = 13),
we must always connect the TK sensor.
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A85 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A85 in the language / languages: English as an attachment in your email.

The manual is 2.45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A85

Atmos A85 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info