810412
34
Zoom out
Zoom in
Previous page
1/66
Next page
EN
www.atmos.cz
34-EN
Operation and Maintenance Manual - EN
This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended. AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
n) S14 = 14….. Reserve function for direct control of solar heating pump from the burner regulation
(boiler terminal board). This function control solar pump when automatic sensor switching function
is activated (S15 = 3), where the boiler is connected with accumulation tank equipped with solar
exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected to the
TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D14P, P14, D15P, P15, D20P, P20, D21P, P21,
D25P and P25
CAUTION - the direct controlling function of solar heating from pellet burner cannot be
used for SP(X) boilers and boilers with burner built into the upper doors. This function also
cannot be used when the pump is simultaneously controlled in the boiler circuit from the
burner regulation (TK sensor cannot be simultaneously in boiler and accumulation tank)
o) S14 = 15….. Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R2 and the compressor.
This function is connected with S6(14), S41, S42, S43, S44, S45, S46, S47 parameter, which must
be checked and configured.
p) S14 = 16….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S6 (14), S41, S42, S43, S44, S45,
S46, S47 parameter, which must be checked and configured.
Special function for turning on reserve output R2 according to the temperature of a concrete
sensor:
a) e.g. function: TS>… means that if the TS sensor temperature is higher then the set value in S52
parameter – Temperature C, reserve output R2 will be activated
b) e.g. function: TS<… means that if the TS sensor temperature is higher then the set value in
S52 parameter – Temperature C, reserve output R2 will be deactivated
c) e.g. function: TS, TV>… means that if the TS and TV sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R2 will be activated (Temperature C = first position (TS), Temperature D = second position (Tv)).
d) e.g. function TS, TK<… means that if the TS and TK sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R2 will be deactivated (Temperature C = first position (TS), Temperature D = second position
(Tk)).
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A85 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A85 in the language / languages: English as an attachment in your email.

The manual is 2.45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A85

Atmos A85 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info