810409
67
Zoom out
Zoom in
Previous page
1/96
Next page
Operation and maintenance manual - EN
EN
www.atmos.cz EN-67
• Parameter S62 – characterizes the function for control of the air valve (flap) with actuator (servo
drive) located in the pellet burner. This valve is operated from the outlet of the burner discharge fan
via the AD04 module integrated in the burner (from serial production - default configuration). The
function is intended for models DCxxGSP, DCxxSP(X), CxxSP, ACxxSP (Model since 2018)... (1)
a) S62 = 0....... funkce OFF (for burners without flap with actuator)
b) S62 = 1....... function ON (for burners with flap with actuator - for models DCxxGSP and
DCxxSP(X), CxxSP, ACxxSP (Model since 2018))
(Burners equipped with internal flap with actuator with AD04 module and the third (additional)
2-pins connector.)
• Parameter S63 – characterizes the function of start delay of the pellet burner (AUTOSTART),
with function of automatic burner start after burnout of the wood. Start delay of the pellet burner
we use in case, that the operator wants to switch the selector switch from the position - wood
to the position - pellets immediately after firing up without waitng till the boiler ran at nominal
output (TSV and TK temperatures not reached). This will always delay the start of the burner
60/120/180/240 minutes. When activating this function the display of the burner shows the time
remaining until the automatic start of the pellet burner (cold condition) or until the change to the
normal function of automatic start characterized with the parameter S34.
In case of that the operation waste gas temperature will be reached (parameter S36 = TSV + 20 K) ends
the countdown of the automatic start and the burner goes directly to normal auto start (parameter S34).
a) S63 = OFF... function switched off - factory stetting
b) S63 = 1... start delay of 1 hour (60 min) - recommended setting
c) S63 = 2... start delay of 2 hour (120 min)
(Setting possibility S63 = OFF, 1 (60 min), 2 (120 min), 3 (180 min), 4 (240 min))
This special function is active in the program version 38 and newer.
INFO - when putting burner into operation with activated function S63 = 1 (or 2, 3, 4) the
plumber may once enter the code 1111 and to skip from AUTOSTART directly to the burner
START (TSV and TK below than defined).
• Parameter S64 - characterizes the temperature of flue gas inside the heat exchanger of the boiler.
It serves to diagnoses the absense of pellets in the boiler tank or shows low output of the boiler. It
is not temperature of flue gas. Function is only for DxxPX (PXxx) boilers, burner profile A25PX.
Do not change… (130 °C)
Parameter S65 - characterizes start up time of the burner in OPERATION mode during which has
to be reached minimal waste gas temperature in the heat exchanger of the boiler set by parameter
S64.
If in this time the boiler does not reach temperature the display shows ALARM SETTINGS –
REFILL PELLETS. In such case check the set output in parameters T4 and T6 and increase it.
In case of low pellets level in the tank fill up the fuel. Function is only for DxxPX (PXxx) boilers,
burner profile A25PX. Do not change… (120 min)
67


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A25 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A25 in the language / languages: English as an attachment in your email.

The manual is 16.33 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A25

Atmos A25 User Manual - German - 70 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info