Operation and maintenance manual - EN
Individual functions:
• Parameter S15 – Operation function of the burner by the two temperatures in the accumulation
tank …(1)
a) S15 = 1… The function is off, the burner works based on the thermoregulator on the boiler panel
b) S15 = 2 …. The function is activated and the pellet burner works based on the two temperatures
(sensors) in the accumulation tank – TV and TS (recommended tank volume: 500 to 1000 l).
The temperature of the bottom sensor (TS) is the temperature at which the burner is switched off
and the fuel burns out (parameter S16).
The temperature of the top sensor (TV) is the temperature at which the burner is switched on again
(parameter S17).
The burner screen displays the TV and TS temperatures.
c) S15 = 3 …. The function is activated and the pellet burner works based on the two temperatures
(sensors) in the accumulation tank – TV and TS (recommended tank volume: 500 to 1000 l).
The temperature of the top sensor (TV) is the temperature at which the burner is switched on again.
The temperature of the bottom sensor (TS or TK) is the temperature at which the burner is stopped.
Whether the burner is switched off based on the TS or TK sensor is decided by the temperature of
the solar panel (TSV) and the temperature in the lower part of the accumulation tank (TS), where a
solar exchange is built-in. If the solar panel can efficiently heat up water in the accumulation tank,
the burner is turned off based on the TK sensor, so that the tank can store energy from the sun.
If the energy delivered from the solar collector drops below a certain limit (temperature), the deactivation
logic of the burner is automatically switched back to be based on the TS sensor (S26 = 1).
However, it is possible to set that the switching may only occur after a certain period of time
(S29 = 2nd digit means the length of delay between switches, in hours). Another variant is to have
the burner work permanently based on the TV and TK temperatures (S26 = 0).
d) S15 = 4 …. The function is off and the burner works based on the TK temperature, protected
by the thermoregulators on the boiler panel. After this function is activated, we need to check and
possibly setup its temperature parameters S18 and S19.
CAUTION - if S15 = 2 not possible to set S6 = 14 a S14 = 14. Je-li S15 = 3 not possible
to set S6 = 11, S14 = 11, S6 = 12, S14 = 12, S6 = 13, S14 = 13. Je-li S15 = 1, S15 = 4 not
possible to set S14 = 14.
(17) TS>
(18) TS<
(19) TV>
(20) TV<
(21) TK>
(22) TK<
(23) TSV>
(24) TSV<
(25) TS,TV>
(26) TS,TV<
(27) TS,TK>
(28) TS,TK<
(29) TS,TSV>
(30) TS,TSV<
(31) TV,TK>
(32) TV,TK<
(33) TV,TSV>
(34) TV,TSV<
(35) TK,TSV>
(36) TK,TSV<
60


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A25 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A25 in the language / languages: English as an attachment in your email.

The manual is 16.33 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A25

Atmos A25 User Manual - German - 70 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info