810409
57
Zoom out
Zoom in
Previous page
1/96
Next page
Operation and maintenance manual - EN
EN
www.atmos.cz EN-57
b) S14 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to an
electrically backed up AB01 ATMOS GSM module controller that will send information that there
is a system fault or the system is not energized. This is the opposite logic (to S14 = 1), which
means that during normal operation the reserve is energized.
c) S14 = 3…… The reserve function as the output function for the burner fan, when the
reserve output is closed, is energized always when the burner fan is running (fan mode only
100 % or OFF). This function is applied if you want the boiler fan or extraction fan in the chimney
to run together with the burner fan. This function is designed for direct control of an fan directly
from the burner (e.g. D80P, P80, DxxPX, PXxx).
d) S14 = 4…… The reserve function as the reversed function of the output for the burner fan,
when the reserve output is off, is not energized always when the burner fan is running. This
function is always activated if you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
AD02 or AD03 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
This setting and connection with AD02 or AD03 module and special connector (jumper to main
switch) is standardly used for DCxxSP(X), CxxSP, ACxxSP boilers with the function for
automatic start after wood is burnt out activated (AUTOSTART – S34 = 1 or S34 = 2). Boiler
exhaust fan is running simultaneously with the pellet burner during the AUTOSTART function.
e) S14 = 5…… Reserve function as the output function for the Z1 ignition spiral when the reserve
copies the run of the ignition spiral.
f) S14 = 6….. Cleaning function of the combustion chamber or grill (flap). If the burner is in the
normal START, RUN and STOP mode, the output is not energized. The output is only energized
for the limited time T11, which continues immediately after the expiration of time T5 in the
STOP mode. It is not used with the A25 burner.
g) S14 = 7….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the
reserve will work independently in accordance with the same program, and therefore it can be
used as a replacement for the damaged output.
h) S14 = 8….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve works in dependence on the status of the actual output for the external worm conveyor.
This means that if the output for the external conveyor gets damaged, the reserve will be switched
off automatically. This function is suitable in situations when you need to control another external
conveyor that supplies (feeds) pellets from a larger distance to the main conveyor from which the
pellets fall directly to the burner.
i) S14 = 9….. Reserve function as the output function for the external worm conveyor, when the
reserve copies the run of the external worm conveyor, but with the difference that it does not cycle,
57


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A25 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A25 in the language / languages: English as an attachment in your email.

The manual is 16.33 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A25

Atmos A25 User Manual - German - 70 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info