INSTALLATION electrical connection
3 phase connection
3 lives with 1 neutral connection (3 1N a.c. 400 V /
50 Hz / Power circuit): The voltage between the phases and the neutral
is 230 V a.c. There is a voltage of 400 V between the lives. Fit a
connecting bridge between the connection points 4-5. Phase 3 carries no
load. Your groups must be fused with at least 16 A (3x). The connecting
power cable must have a minimum core cross section of 2,5 mm
2
.
3-phase connection (3 a.c. 230 V / 50 Hz):
The voltage between the phases and the neutral is 230 V a.c.
Install connecting bridges between the connection points 4-5. Your
groups must be fused with at least 16 A (3x). The connecting power
cable must have a minimum core cross section of 2,5 mm
2
.
right zones
ignition transformer/
left zones
right zones
ignition transformer/
left zones
176 177
INSTALLATION
The appliance can be connected in the following ways:
2 phase connection
2 lives with 2 neutrals connection (2 2N a.c. 230 V /
50 Hz / Cooking circuit): The voltage between live and neutral is
230 V a.c. There may be a voltage of 0 V between the phases if they are
connected to the same phase in the meter cupboard but also 400 V if
they are connected to 2 different phases. Your groups must be fused with
at least 16 A (2x). The connecting power cable must have a minimum
core cross section of 2,5 mm
2
.
2 lives with 1 neutral connection (2 1N a.c. 400 V /
50 Hz): The voltage between the phases and the neutral is 230 V a.c.
Between the lives there is a voltage of 400 V. If there is not a voltage of
400 V between the lives, two wires have been taken from the same live in
the meter cupboard and the hob must be connected with two neutral
wires, as indicated above under 2 lives with 2 neutrals. Install a
connecting bridge between the connection points 4-5. Your groups must
be fused with at least 16 A (2x). The connecting power cable must have a
minimum core cross section of 2,5 mm
2
.
electrical connection
right zones
ignition transformer/
left zones
right zones
ignition transformer/
left zones
89


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATAG IG907 1MX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATAG IG907 1MX in the language / languages: Dutch as an attachment in your email.

The manual is 3,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info