This button regulates the heating characte-
ristics of the heating circuit in relation to out-
door temperature.
The adjustment is dependent of the plant installation and
shows the relation between outdoor temperature and
heat generator (boiler) temperature.
The slope sets the change of the supply temperature, if the
outdoor temperature changes for 1 K.
Re-entry into the standard display is done be pressing
the button
££
again or automatically after approx.
60 seconds.
Setting the heating characteristics (heating curve)
Page 11
Diagram of heating curves
2.00
1.75
1.50
1.25
1.00
0.75
0.50
0.20
20 16 12 8 4 0 -4 -8 -12 -16 -20 Outdoor temp.(°C)
100
90
80
70
60
50
40
30
20
Heat generator temperature (°C)
(factory preset)
1.50
HHCC
HHEEAATT.. CCUURRVVEE
Setting range: OFF (heating circuit eliminated)
0,20...3,50
Factory preset: 1,50
Modify
Slope
Store modification
Note: The heating slope should be modified only in small steps
and left for a while until steady condition can be obtained.
Changes to the slope should be made in intervalls of 0.1
every 1 or 2 days.