FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 31
6.2.3 Supervised outputs A
These outputs provide 24 VDC when active. A red LED displays the state of the outputs.
(Refer to sections 3.2.1 and 3.2.3 for technical information on these outputs.)
Figure 20: Supervised relay output’s connection on SD2000 common I/O board
1. Fault routing (Out4)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
* Active in normal position
3. Fire routing device (Out2)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
2. Fire protection device (Out3)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
4. Fire alarm device (Out1)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
6.2.4 Relay outputs B
OUT1 / OUT2 / OUT3 (Refer to positions 7, 8, 9 in figure 13.)
Two configurations are available. The configuration is determined by jumper settings.
An LED indicates the state of the output (LED ON = output active).
Figure 21: Two configurations for relay outputs 1-3 B
Outputs CONFIG. 1 CONFIG. 2
Sounders OUT 1 J12 in
J13 out
J12 out
J13 in
" J18 out
J19 out
Fire Brigade OUT 2 J2 in
J3 out
J2 out
J3 in
" J18 out
J19 out
Fire Protection OUT3 J4 in J4 out
33


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aritech FP-FR1200 Series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aritech FP-FR1200 Series in the language / languages: English as an attachment in your email.

The manual is 4,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info