24 FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Figure 11: Class "B" Single direction loop (Star configuration)
Figure 12: Class B single direction loop with tee offs
A maximum of 126 detectors (900 Series) or 128 detectors (2000 Series) can be
connected to a loop. For combinations of fire sensing devices, monitoring controllers and
input/output devices, the maximum number of addressable units must be calculated.
Please refer to the Installation Manual of the 900 Series and 2000 Series detectors.
"
EN54 specifies that a short circuit or an interruption in a detection circuit
cannot prevent the indication of a fire alarm from more than 32 fire detectors
and/or manual call points.
Therefore, when more than 32 detectors are connected to one loop, an
isolator should be placed at least at every 32 devices. In that case, a class A
configuration (no Tee Offs) should always be used.
" EN54 specifies that in case of a system fault, not more than 512 fire
detectors and/or manual call points and their associated mandatory functions
shall be affected. Taking this into consideration, the amount of detectors per
panel should be limited to 512.
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aritech FP-FR1200 Series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aritech FP-FR1200 Series in the language / languages: English as an attachment in your email.

The manual is 4,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info