FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 53
8.2 Procedure for switching on
1. Switch the main power on at the power supply or connect the 24 V to the 24 V supply
board.
2. The internal buzzer will sound and the product code will be displayed on the LCD
screen along with the revision of host firmware, firmware code and the creation date
of the firmware.
If the above does not occur, DO NOT proceed. Check that the mains supply is
present and that the fuses are good.
3. Switch the battery On/Off switch to the ON position (230 V model only).
4. Check that the battery float voltage is 27.6 V. If the voltage is significantly less, then
check:
Are the batteries flat?
Are there possible overloads in the field?
5. If there are visible signs of the power supply overheating, then do not proceed.
Disconnect the field wiring and batteries, and eliminate the cause of the problem.
6. The fire panel will perform internal checks. Any failures occurring will be reported on
the LCD screen.
Observe the total number of faults reported on line 8 of the LCD screen.
It is expected to have at least two faults reported:
Memory unlocked
Service switch ON
7. Use the key to view the faults existing.
8. All faults (except for the two above) should be eliminated before proceeding further.
Use the [RESET] button to obtain a new fault report each time.
Possible faults that can occur on switch ON are:
y Loop overload - Check the affected loop for short circuits
y Earth fault - Check/eliminate the fault
y Battery fail - Check battery charging
y Sounders or fire brigade - Check 3K3 termination resistors
y Short circuit or open circuit termination resistors
y Specific device faults - Check device
y Double address - Note address of device and check
9. Enable the loop devices of the FP2000 fire panel in one of three methods:
Individually manually using the Device Set-up Menu.
Set default using the System Default Set-up.
Program by means of a laptop computer using the RS232 port.
10. Eliminate any fire alarms and communications alarms reported.
55


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aritech FP-FR 2000 Series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aritech FP-FR 2000 Series in the language / languages: English as an attachment in your email.

The manual is 4,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info