6. INSTALLATION
6.1 LOCATION OF THE APPLIANCE
The following list gives guidance to locating the Nuos heat pump.
1. The NOUS must be installed in a dwelling or suitable outhouse, it
must not be installed outside and/or where it could be subjected to
temperatures below 1°C.
2. The Nuos heat pump is rated as an IPX4. It must not be installed in
Bathroom Zone 1. It can be installed in Zone 2, however, the electrical
switch must be installed in Zone 3.
3. Units without an air exhaust duct must be installed in rooms with a
volume greater than 20m³ and a floor area greater than 8m².
4. The practical limit of 5.12m³ (as stated on page 18) is the minimum
room volume the appliance should be installed in, the volume is based
on quantity of refrigerant in the system. In the event of a sudden
release of refrigerant then the minimum room volume will make it
safer for the engineer. Where the room volume is less than the
practical limit never fit a self-closing device to the door.
5. The effects of cooled air entering the room must be considered. The
operating temperature range of the appliance is between - 5ºC and
42ºC. Operating the appliance below the minimum temperature
compromises the efficiency and can lead to frosting of the heat pump.
6. If the unit is to be installed in a room with a volume of less than 20m³
and/or a floor area less than 8m² then an exhaust duct must be fitted.
Also provision must be provided for air to enter the room i.e. vent or
air brick. The exhaust can be ducted to outside the dwelling or to
another room.
7. Do not install the unit in rooms with other appliances that require
ambient air; e.g. conventional flue boilers, gas fires and water heaters.
(Only applies where air is drawn from a room or internal space).
8. Study the water connections and electric supply and consider the
plumbing and wiring layouts for optimum positioning of the unit.
9. The TPRV, PRV discharge pipe and condensate drain pipe must be
plumbed to a suitable drain, normally outside the dwelling. The PRV
discharge must comply to Building Regulati3ns, see 6.13.
10. To function correctly, the unit must be installed with suitable minimum
clearances. These are 100mm behind the unit, 400mm to each side
and 50mm above, see fig. 6.16A.
11. The floor on which the unit is to be standing must be capable of
supporting (locally) the weight of the full unit. Do not install the
appliance on a chipboard floor.
12. The unit has an electric fan; some vibration and sound is inevitable,
some types of floor construction may produce adverse sound levels.
A sound reducing pad can be used between the Nuos and the floor,
not supplied.
The air supply for the Nuos enters through a round socket at the left hand
side of unit. The air could be drawn from within the room or ducted from
another room/internal space within the dwelling or more typically from the
outside. See 1.8
The minimum volume of the room/space that air is being drawn must
have a minimum volume of 20m³. The effects of drawing warm air from
the room must be considered.
Do not draw air from rooms containing appliances that require ambient air
for combustion, typically conventional flue boilers, water heaters and gas
fires.
6.2 AIR SUPPLY
See examples section 1.13.
IMPORTANT
Hard Water
Where the mains total water
hardness exceeds 200 ppm,
provision should be made
to treat the feed water to
reduce the rate of limescale
accumulation.
23


Need help? Post your question in this forum.

Forumrules
1

Forum

ariston-nuos-plus

Reset search

  • Pas d’eau chaude
    Marqué boost dans l’appareillante Submitted on 12-11-2021 at 22:31

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston NUOS PLUS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston NUOS PLUS in the language / languages: English as an attachment in your email.

The manual is 1,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ariston NUOS PLUS

Ariston NUOS PLUS User Manual - German - 33 pages

Ariston NUOS PLUS User Manual - Dutch - 35 pages

Ariston NUOS PLUS User Manual - French - 34 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info