24
GB
15 m max
VACUUM PUMP
SERVICE CONNECTION
GAS VALVE
SERVICE CONNECTION
LIQUID
VALVE
COCK
PROTECTION CAPS
3 m
TIGHTENING TORQUE FOR THE FLANGE CONNECTIONS
Pipe Tightening torque
[kgf x cm]
Corresponding effort
(using a 20 cm spanner)
6.35 mm (1/4”) 160 - 200 wrist force
9.52 mm (3/8”) 300 - 350 arm force
12.70 mm (1/2”) 500 - 550 arm force
15.88 mm (5/8”) 630 - 770 arm force
TIGHTENING TORQUE FOR PROTECTION CAPS
Tightening torque [kgf x cm]
Service connection 70-90
Protection caps 250-300
IMPORTANT CHECK FOR ANY REFRIGERANT LEAKS
Once you have made the connections, open the cocks so that the gas fi lls
the piping and always check all piping against leaks using a leak detector
(risk of personal injury from cold burns).
LENGTH OF THE PIPING
The maximum length of the connection piping varies according to the mod-
el. When the piping is longer than 7,5 m, pay attention to the quantity of
refrigerant that should be added for each metre. Should the external unit
have to be installed higher up than the internal unit with a difference in
height of more than 3 m, then traps should be fi tted on the return piping so
that the oil trickling down the pipe walls deposits in the trap until the latter
is full. The oil plug that forms will be shot upwards by the gas.
2.9 Making a vacuum and checking the tightness
The air must be expelled from the circuit using a vacuum pump, pump tran-
sition fi tting and pressure gauge assembly which are suitable for R410A.
Ensure that the vacuum pump is fi lled with oil to the level indicated by the
oil gauge and that both cocks on the external unit are shut:
1. unscrew the caps on the cocks of the two-way and three-way valves, and
on the service valve;
2. connect the vacuum pump to the small service valve in the three-way
valve of the external unit;
3. once you have opened the corresponding valves on the pump, start the
latter and leave it to operate. Make a vacuum for approximately 20/25
minutes;
4. make sure the pressure gauge shows -0.101 MPa (-760 mmHg);
5. shut the cocks on the pump and turn it off. Check that the needle on the
pressure gauge does not move for approximately 5 minutes. If the nee-
dle moves, this means that air is seeping into the system, and you must
check all connections are tight enough and that the piping connections
were all made correctly; then repeat the procedure from step 3;
6. disconnect the vacuum pump;
7. open the cocks on the two-way and three-way valves fully;
8. screw the plug tightly to the service outlet ensuring that it is well sealed;
9. after having tightened all the plugs, check that there are no gas leaks
around their circumference.
WARNING:
Always protect the connection cables and pipes to prevent damage to
them, as they could cause gas leaks when damaged (personal injury
from cold burns).
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston MIROS 35 XC4-I at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston MIROS 35 XC4-I in the language / languages: English, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 1,71 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info