of withstanding high temperature discharges of water 3 m from any plastic guttering
systems that would collect such a discharge (tundish visible).
iv) Where a single pipe serves a number of discharges, such as in blocks of flats, the
number served should be limited to not more than 6 systems so that any installation
can be traced reasonably easily. The single common discharge pipe should be at least
one pipe size large than the largest individual discharge pipe to be connected. If
unvented hot water storage systems are installed where discharges from safety
devices may not be apparent i.e. in dwellings occupied by the blind, infirm or disabled
people, consideration should be given to the installation of an electronically operated
device to warn when discharge takes place. Note: The discharge will consist of
scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may
be damaged by such discharges.
16
Valve outlet size Minimum size of
discharge pipe D1*
Minimum size of
discharge pipe D2*
from tundish
Maximum
resistance allowed,
expressed as a
length of pipe (i.e.
no elbow or bends)
Resistance created
by each elbow or
bend
G 1/2 15 mm 22 mm
28 mm
35 mm
Up to 9 m
Up to 18 m
Up to 27 m
0.8 m
1.0 m
1.4 m
G 3/4 22 mm 28 mm
35 mm
42 mm
Up to 9 m
Up to 18 m
Up to 27 m
1.0 m
1.4 m
1.7 m
G 1 28 mm 35 mm
42 mm
54 mm
Up to 9 m
Up to 18 m
Up to 27 m
1.4 m
1.7 m
2.3 m
Table 2
Sizing of copper discharge pipe D2 for common temperature valve outlets.
Worked example
The example below is for a G 1/2 temperature & pressure relief valve with a discharge
pipe (D2) having 4 no. elbows and length of 7 m from the tundish to the point of
discharge.
From Table 2
Maximum resistance allowed for a straight length of 22 mm copper discharge pipe
(D2) from G 1/2 T & P valve is 9 m.
Subtract the resistance for 4 no. 22 mm elbows at 0.8 m each = 3.2 m.
Therefore the maximum permitted length equates to: 5.8 m.
As 5.8 m is less than the actual length of 7 m therefore calculate the next
largest size.
Maximum resistance allowed for a straight length of 28 mm pipe (D2) from G 1/2 T &
P valve equates to: 18 m.
Subtract the resistance for 4 no. 28 mm elbow at 1.0 m each = 4 m.
Therefore the maximum permitted length equates to: 14 m
As the actual length is 7 m, a 28 mm (D2) copper pipe will be satisfactory.
16


Need help? Post your question in this forum.

Forumrules
1

Forum

ariston-aures-slim-multi

Reset search

  • Where can i find if heater is switched on Please Submitted on 2-12-2021 at 20:19

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston Aures Slim Multi at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston Aures Slim Multi in the language / languages: English as an attachment in your email.

The manual is 2,68 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info