665465
20
Zoom out
Zoom in
Previous page
1/30
Next page
V 11/15
50
Outdoor unit
1. Choose a location where the noise and airflow produced by the outdoor unit will not annoy neighbours.
2. The location should be well ventilated and dry; the outdoor unit must not be exposed to direct sunlight
or strong winds.
3. The site should be able to support the weight of the outdoor unit.
4. Check that the installation complies with the requirements of the dimensional drawing for installation.
5. Choose a location out of the reach of children and away from animals or plants. If this is not possible,
install safety fencing.
Electrical connection requirements
Safety precautions
1. Electrical safety standards must be met when installing the unit.
2. Use a power supply circuit and circuit breaker that comply with local safety regulations.
3. Make sure that the power supply matches the requirements of the air conditioner. An unstable
power supply or incorrect wiring may result in a fault. Install suitable power cables before
switching on the air conditioner.
4. Correctly connect the live, neutral and earth wires to the power outlet.
5. Disconnect the power supply before carrying out any work on the electrical circuit or carrying
out any safety work. For models with a plug, make sure the plug is easily accessible after
installation.
6. Do not connect the power before installation is complete.
7. Do not use the appliance if the power cable or plug are damaged. If the power cable is
damaged it must be replaced by the manufacturer, retailer or other qualified person to avoid a
hazard.
8. Since the temperature of the cooling circuit is high, keep the interconnecting cable away from
the copper pipe.
9. The unit must be installed in accordance with national wiring regulations.
10. Installation must only be performed by trained individuals in accordance with regulations.
Earthing
1. The air conditioner is a Class I appliance. The unit must be earthed with an appropriate
device by a qualified technician. Ensure the unit is always properly earthed. Otherwise
electric shock may result.
1. The green-yellow wire of the air conditioner is the earthing wire and may not be used for other
purposes.
2. The earth resistance must meet national standards for electrical safety.
3. The unit must be positioned so that the plug is accessible.
4. An all-pole isolating switch with a minimum contact gap of 3mm in each pole must be
connected to the fixed cable.
5. Install a circuit breaker of sufficient capacity and note the following table. The air switch must
include a thermal and magnetic trip function to protect against short circuits and overloads.
(Warning: do not use only the fuse to protect the circuit)
Air conditioner Circuit breaker capacity
09-12K 16 A
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Argo Wall Dual 18000 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Argo Wall Dual 18000 in the language / languages: English as an attachment in your email.

The manual is 2,8 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Argo Wall Dual 18000

Argo Wall Dual 18000 User Manual - German - 34 pages

Argo Wall Dual 18000 User Manual - French - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info