48V 11/22
TABLE A - Minimum room area (m2)
Maintenance notes
Check whether the maintenance area or the room area meet the requirement of “table a” the unit is only allowed
to be operated in rooms that meet these requirements.
Check whether the maintenance area is well-ventilated. The continuous ventilation status should be kept during the
entire operation process.
Check whether there is a re source or potential re source in the maintenance area. Running re is prohibited in
the maintenance area and the “no smoking” sign should be hanged.
Check whether the warning sign is in good condition, otherwise replace it.
Welding
If it is necessary to cut or weld the refrigerant system pipes in the maintenance procedures, please follow the steps
here below:
Shut down the unit and cut power supply
Eliminate the refrigerant
Vacuum with a vacuum machine
Clean the pipes with the N2 gas
Cut and weld or
Bring the unit to a service centre for welding
The refrigerant should be recycled in a specialized storage tank.
Make sure there aren’t any free ames near the outlet of the vacuum pump and that it’s well-ventilated.
Filling the refrigerator circuit
Use refrigerant lling appliances specialized for R32. Make sure that different kinds of refrigerant don’t contaminate
one another.
The refrigerant tank should be kept upright when lling with the refrigerant.
Stick the label on the system after lling is nished.
Don’t overll.
After lling is nished, please test the unit for leakage detection before the operation test; another test for leakage
detection should be carried out when the refrigerant is removed.
Safety instructions for transportation and storage
Please use a ammable gas detector to check before unloading and opening the container.
No re source and no-smoking.
According to the local rules and laws.
Before installating, please contact with local authorized maintenance center, if unit is not installed by the authorized
maintenance center, the malfunction may not solved due to discommodious contact.
The air conditioner must be installed by professionals according to the national wiring rules and this manual.
Refrigerant leak test must be made after installation.
To move and install air conditioner to another place, please contact our local special service center.
SAFETY PRINCIPLES FOR INSTALLATION
Fire prevention device shall be prepared before installation.
Keep installing site ventilated (open the door and window)
Ignition source, re, smoking and mobile phones are not allowed to exist in area where R32 refrigerant located.
CAUTION
Minimum room
area (m2)
Charge amount (kg) 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5
Floor location / 14.5 16.6 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6
Window mounted / 5.2 6.1 7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3
Wall mounted / 1.6 1.9 2.1 2.4 2.8 3.1 3.4 3.8 4.2 4.6 5 5.5 6
Ceiling mounted / 1.1 1.3 1.4 1.6 1.8 2.1 2.3 2.6 2.8 3.1 3.4 3.7 4
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Argo Hi-comfort Plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Argo Hi-comfort Plus in the language / languages: English as an attachment in your email.

The manual is 3.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Argo Hi-comfort Plus

Argo Hi-comfort Plus User Manual - Italian - 31 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info