Setting of proportional cooling band
Index - String
MIN
value
MAX
value
Parameter function
1 °C 20 °C
This parameter indicates the proportional band applied to the cooling set; this band produces the opti-
mised management of the compressor, only switching it on if the inlet/outlet water temperature (depen-
ding on the type of control set by parameter (0) in the installer menu) is greater than the cooling work
set (parameter (1) user menu) plus the value of this parameter.
Setting of proportional heating band
Index - String
MIN
value
MAX
value
Parameter function
1 °C 20 °C
This parameter indicates the proportional band applied to the heating set; this band produ-
ces the optimised management of the compressor, only switching it on if the inlet/outlet water
temperature (depending on the type of control set by parameter (0) in the installer menu) is
less than the heating work set (parameter (3) user menu), minus the value of this parameter.
In cooling only units, this parameter is displayed but it cannot be modified.
Settings made on the basis of outside temperature
Index - String
MIN
value
MAX
value
Parameter function
03
This setting activates the algorithm of compensation of the work setting:
(°C)
(°C)
SET (F)
SET (H)
SET (G) SET (I)
In cooling mode, the work setting is cal-
culated automatically on the basis of the
outside temperature, following the logic
highlighted in the diagram.
(°C)
(°C)
SET (J)
SET (N)
SET (L) SET (O)
In heating mode, the work setting is cal-
culated automatically on the basis of the
outside temperature, following the logic
highlighted in the diagram.
SF1
SF2
TF1 TF2
SC1
SC2
TC1 TC2
SF1: index (6) user menu;
SF2: index (8) user menu;
TF1: index (7) user menu;
TF2: index (9) user menu;
SC1: index (A) user menu;
SC2: index (C) user menu;
TC1: index (B) user menu;
TC2: index (d) user menu;
Parameter visible ONLY on units suitable for the production
of hot water
Parameter visible ONLY on units suitable for the production
of DHW
Parameter visible ONLY on units with condensation control
device on board
Parameter ONLY visible on units fitted with twin compressor
Parameter ONLY visible on units fitted with inverter com-
pressor
Setting heating mode temperature set
Index - string
Value
MIN
Value
MAX
Parameter function
25 °C (*)
This parameter indicates the active work set value in the heating mode. This
parameter is displayed in the cooling only units but cannot be modified.
(*):
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes
70°C in order to allow insertion of a set-point for boiler adjustment;
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aermec MODUCONTROL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aermec MODUCONTROL in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info