Protect PV.500 Operating Instructions
26 of 70 80000031354 BAL
5 System Function
5.1 Description of Sequence Control
As soon as the equipment's control module is supplied with
voltage, sequence control starts.
Initially, the load interrupter switch Q4 remains open. Once the
initialisation phase is complete and if no deactivating faults are
pending, the load interrupter switch Q4 is closed. During
subsequent operation, the switch is only opened by deactivating
faults (Æ chapter 6).
The inverter output contactor K7 remains open initially. The
contactor is switched by the sequence control.
The figure below provides a graphical illustration of the sequence
control statuses.
OFF
Waiting for feed
conditions
Fault
Operation
Night
Feed-in
conditions met
Operating
conditions
no longer
met
ON command
OFF command OFF command
OFF command
Daytime detection
Night-time detection
Fault
Fault
Fault
acknowledgement
OFF command
Maintenance
Delay
complete
Fault
Figure 6 Sequence control
5.1.1 The "OFF" Status
The equipment has been switched off logically via the DOU or the
master control unit.
The equipment is running without faults, the monitoring systems
are not activated.
In this status, no power is fed into the mains.
Possible change of status:
The status can be switched from "OFF" to "Waiting for feed
conditions" by switching the equipment on via the DOU and the
master control unit.
5.1.2 The "Waiting for Feed Conditions" Status
The values of the DC voltage on the PV cells, the mains voltage
and the mains frequency are observed by the equipment.
The monitoring parameters values are checked regularly.
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for AEG Protect PV 500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of AEG Protect PV 500 in the language / languages: English as an attachment in your email.

The manual is 1,99 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of AEG Protect PV 500

AEG Protect PV 500 User Manual - German - 136 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info