3.8.1 How to operate Aduro-tronic
When lighting
When lighting a fire in the wood burning stove for the first time, the maximum
amount of primary air will be needed to light the fire. For that reason, the
primary damper can be kept “forcibly open”. This is done by pulling the primary
damper forward as far as possible and then fixing it with the Aduro Key (see
illustration). When the stove is warm and a layer of embers has been created
on the bottom of the combustion chamber, the Aduro-tronic can be set to the
automatic position, i.e. the Aduro Key can be removed.
Alternatively, you can leave the door ajar the first minutes during lighting the
fire (without the key).
When stoking
Each time fresh wood is put in the stove, a precise amount of primary air will
be allowed in for the first few minutes. What’s more important is that the
primary air is not allowed in for too long. This is to ensure optimum
combustion. The Aduro-tronic control will ensure intake of primary air at the
right tempo. The automatic is activated by pulling the primary damper out each
time fresh wood is put in the stove. The automatic closes then the primary air
gradually.
Regulation of the Aduro-tronic control
The control is pre-set to allow primary air intake for the first 5 minutes. This
setting has been used during testing at the Danish Technological Institute using ‘standard’ sized logs and with
maximum moisture content of 18%. Standard size logs are approx. 30 cm long and 10 x 10 cm in thickness. A
standard chimney was also used for testing. In practice, such circumstances can differ, which is why the Aduro-
tronic control can be adjusted to your circumstances. If you want a slower intake of primary air: (e.g. for a slower
flue draught, larger sized wood or for longer intervals between stoking) Adjust the screw on the front of the control
level using a small allen key to slow closure rate. If the screw is turned to the right closing time is increased and if
turned to the left closing time is reduced. The Aduro-tronic must be closed within 6 minutes.
3.9 Ventilation/fresh air supply
In order for the wood burning stove to function at optimum efficiency, air is needed for the combustion process.
There must be sufficient fresh air coming into the room containing the wood burning stove. In very well-insulated
houses, or houses with powerful cooker hoods and/or air conditioning systems, a vacuum can be created around
the wood burning stove, leading to smoke leakage and poor combustion. In these circumstances, it might be
necessary to open a window to provide air for combustion and to equalize the vacuum. Alternatively, you could fit
an air vent in the room containing the wood burning stove. The amount of air needed for combustion is 25 m3/h.
4.0 The chimney
Data for chimney calculation:
Wood
Flue temperature at [20 C]
245
Chimney draught at testing power
[mbar]/[Pa]
0.12/12
Flue gas mass flow [g/s]
5,7
The optimum combustion is achieved at a constant chimney draught of 0.10 to 0.14 mbar measured in the flue pipe
above the stove. There are many factors that affect the chimney draught, including the outside temperature, wind
strength and surrounding buildings. If it is impossible to establish a sufficiently natural chimney draught, the
chimney can be fitted with a smoke extractor. If the chimney draught is too strong, a damper can be fitted to
regulate the chimney draught. Contact your local chimney sweep for more advice.
There are no requirements with respect to specific chimney heights, but a chimney must be tall enough to provide a
good draught above 12 Pa. If the recommended chimney draught is not achieved, there may be problems with
smoke out of the door by firing.
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Aduro 9-3 Lux at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Aduro 9-3 Lux in the language / languages: English, German, Danish, French, Norwegian as an attachment in your email.

The manual is 3.42 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info