WaterMaster 25 - 35 - 45 - 70 - 85 - 120 : A1006482 - 664Y7300 • D
LOCKING CODES
Codes Description of the fault Solution for the fault
E 01 Failed ignition: The burner failed to light after 5 ignition attempts.
1. Check gas supply to appliance.
2. Check Ignition cable connection in control box.
3. Check electrode for defects, and distance between the pins.
4. Check gas valve and electrical connections to gas valve.
E 02 False ame: Flame detected prior to ignition. 1. Check good electrical ground connection to unit.
2. Check electrode for pollution and deposition of dirt.
E 03 High Boiler temp. : The appliance temperature exceeds 105°C
Correct condition which caused high temperature or limit to open.
1. Check water ow in the system (radiator valves).
2. Check Pump and pump electrical connections.
E 05 Blower speed: Blower speed not correct or speed signal is not received by ACVMax.
1. Check blower and wiring harness.
2. Under normal condition if actual fan speed is 1000 rpm dierent from set fan speed an error is displayed (after 60sec
in running and after 30 sec. at startup).
3. Only exception when actual fan speed > 3000 rpm at max. PWM.
E 07 High Flue temp.: Flue temperature exceeds high limit. 1. Heat exchanger may require cleaning.
2. Appliance will automatically reset once flue temperature returns to normal range.
E 08 Flame Circuit Error: Flame circuit test failed
1. Turn appliance o.
2. Check and clean the electrode.
3. Check ignition and grounding cables are rmly connected.
E 09 Gas valve circuit error: Gas valve circuit test failed. 1. Check the gas valve and wiring harness.
2. If the problem persists replace the ACVMax circuit board.
E 12 Internal Fault: EEPROM misconguration 1. Turn unit o and on to resume normal operation.
2. If the problem persists replace the ACVMax circuit board.
E 13 Reset limit reached: Resets are limited to 5 every 15 minutes. 1. Turn unit o and on to resume normal operation.
2. If the problem persists replace the ACVMax circuit board.
E 15 Sensor Drift: Supply or return sensor reading has drifted. Check supply and return temperature sensors and wiring harness.
E 16 Supply Sensor Stuck: Supply sensor reading is not changing. 1. Check supply temperature sensor and wiring harness for shortcuts or other defects.
2. Check waterow and the temperature balance in the system, because CH supply temperature does not change.
E 17 Return Sensor Stuck: Return sensor reading is not changing.
1. Check return temperature sensor and its position, check wiring harness for shortcuts or other defects.
2. Check waterow and the temperature balance in the system, because CH return temperature does not change.
3. Failure may happen at low output capacity when supplying from a big tank !
E 18 Sensor Failure: Supply or return sensor reading changed very rapidly. Check supply and return temperature sensors and wiring harness.
E19 Flame Failure: Flame failure during start up phase
Flame loss after start up of the appliance.
1. Check the ue system for blockage and check the adjustment of the appliance (CO2 high 8,8 +/-0,2%, CO2 low 8,6+/-
0,2% measured with front casing open).
2. Also check the Ignition / Ionisation rod ( distance to the burner / pollution)
E 21 Internal Control Fault: A / D conversion error. Turn unit o and on then press OK to resume normal operation.
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ACV Watermaster at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ACV Watermaster in the language / languages: English as an attachment in your email.

The manual is 7.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of ACV Watermaster

ACV Watermaster Usermanual and installation guide - German - 48 pages

ACV Watermaster Usermanual and installation guide - Dutch - 52 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info