620410
13
Zoom out
Zoom in
Previous page
1/68
Next page
en
13
System Control - ACVMax: 660Y2800 • B
EN
FR
NL
ES
IT
DE
PL
RU
APPLIANCE DESCRIPTION AND OPERATION
CH & DHW Settings / Heating Settings (Cont’d)
Heating Settings
Outdoor Curve / Warmest Day 18°C
CH2/CV2 Circuit Enabled
CH2 Max. Setpoint 60°C
CH2 Min. Setpoint 27°C
Warm Weather Shutdown
O
Circulation Pump Permanent Disabled
Heating Settings
CH2/CV2 Circuit Enabled
CH2 Max. Setpoint 60°C
CH2 Min. Setpoint 27°C
Warm Weather Shutdown
O
Circulation Pump Permanent Disabled
CH Post Pump Time 5 min
CH Post
Pump Time
5 min
O 30 min
CH Post Pump Time sets how long the central heating circulators will continue to op-
erate at the completion of a heating call. Refer to “Pumps on page 32 to know which
pumps will continue to operate. Any call during the CH Post Pump Time will be ignored
until the post pump has completed. The CH Post Pump Time feature allows the heat re-
maining in the boiler at the completion of a call to be sent to the heating system, which
will improve the overall eciency of the system.
Press the LEFT or RIGHT buttons to adjust the CH Post Pump Time then press the OK
button to store the setting.
Default: 5 min
Heating Settings
CH2 Max. Setpoint 60°C
CH2 Min. Setpoint 27°C
Warm Weather Shutdown
O
Circulation Pump Permanent Disabled
CH Post Pump Time 5 min
Freeze Protection Enabled
Freeze Protection
Enabled
Disabled
The Freeze Protection menu allows the feature to be enabled and disabled. The built-in frost
protection mechanism activates the system pumps as soon as the ow temperature [NTC1
probe] drops below 7°C. As soon as the ow temperature is at 5°C, the burner starts up until the
ow temperature rises above 15°C. The pumps continue to run for around 10 minutes.
Press the UP or DOWN buttons to select Enabled or Disabled then press the OK button to
store the setting.
Enabled The Frost Protection feature protects the installation from freezing at a prede-
termined system ow temperature.
DisabledThe Frost Protection feature is disabled. Only the pumps operate.
Default: Enabled
Heating Settings
CH2 Min. Setpoint 27°C
Warm Weather Shutdown
O
Circulation Pump Permanent Disabled
CH Post Pump Time 5 min
Freeze Protection Enabled
Frost Protection Setpoint -30°C
Frost Protection
Setpoint
-30°C
-30°C 10°C
Frost Protection Setpoint allows to dene the outside air temperature at which the an-
ti-freeze function is activated (only available if an outdoor temperature sensor is connected).
The pumps are activated when the outside temperature drops below the threshold dened
in this menu.
Press the LEFT or RIGHT buttons to adjust the Freeze temperature Setpoint then press
the OK button to store the setting.
In order to enable the Prestige boiler to protect the whole system against freezing, all
the valves of the radiators and the convectors should be completely open.
Default: -30°C
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ACV Prestige at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ACV Prestige in the language / languages: English as an attachment in your email.

The manual is 13,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info