CodesDescription of the faultSolution for the fault
E 79Mix-circuit sensor Open
1. Check Mix circuit temp. sensor and wiring harness for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 80Return > Supply: Return temperature is higher than supply temperature. Conrm water ows in boiler return and out boiler supply.
E 81Sensor Drift: Supply and return temperatures are not equal.
1. Check water is owing through boiler.
2. Wait a few minutes for the water to equalise the temperature, the boiler will automatically reset once temperatures be-
come equal.
3. If boiler doesn't reset, check the NTC's and check the wire harness, replace if necessary.
E 87External Limit Open: An external boiler limit has opened.
1. Correct condition which caused limit to open, then reset boiler.
2. The boiler needs to be reset once external limit closes.
E 89Incorrect Setting: A parameter setting is outside the settings range.
1. Review CH & DHW settings and correct as necessary.
2. The boiler will automatically reset once corrected.
E 90Firmware Mismatch: Control module and display rmware versions are incompatible.One or several components are not compatible with the system. Replace mismatched component(s).
E 91
System Sensor Shorted: A short circuit has been detected in the system temperature
sensor circuit
1. Check system temperature sensor and wiring for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 92
System Sensor Open: An open circuit has been detected in the system temperature
sensor circuit.
1. Check system temperature sensor and wiring for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 93
Outdoor Sensor Shorted: A short circuit has been detected in the outdoor tempera-
ture sensor circuit.
1. Check outdoor temperature sensor and wiring for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 94Internal Display Fault: Display memory errorTurn unit o and on to resume normal operation.
E 95Supply Sensor Error: Supply sensor reading is invalid
1. Check wiring between display and control module.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 96
Outdoor Sensor Open: An open circuit has been detected in the outdoor tempera-
ture sensor circuit.
1. Check outdoor temperature sensor and wiring for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 97Cascade Mismatch: Cascade conguration has changed.
1. Run autodetection if change was intentional, or else check wiring between boilers.
2. Boiler will automatically reset once repaired.
E 98Cascade Bus Error: Communication with other boilers has been lost.
1. Check wiring between boilers.
2. Boiler will automatically reset once repaired.
E 99
Controller Bus Error: Communication between boiler display and control module has
Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.
Product:
Forumrules
To achieve meaningful questions, we apply the following rules:
First, read the manual;
Check if your question has been asked previously;
Try to ask your question as clearly as possible;
Did you already try to solve the problem? Please mention this;
Is your problem solved by a visitor then let him/her know in this forum;
To give a response to a question or answer, do not use this form but click on the button 'reply to this question';
Your question will be posted here and emailed to our subscribers. Therefore, avoid filling in personal details.
Register
Register getting emails for ACV Prestige Excellence at:
new questions and answers
new manuals
You will receive an email to register for one or both of the options.
Get your user manual by e-mail
Enter your email address to receive the manual of ACV Prestige Excellence in the language / languages: English as an attachment in your email.
The manual is 13,24 mb in size.
You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.
The manual is sent by email. Check your email
If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.
The email address you have provided is not correct.
Please check the email address and correct it.
Your question is posted on this page
Would you like to receive an email when new answers and questions are posted? Please enter your email address.