4
EN
GENERALE
The units are delivered fully assembled, tested and packed on a timber base with shockproof edges and protected by heat-shrunk plastic
film. On reception and after unpacking, check the equipment for damage.
For transport purposes, refer to the weights and dimensions given below.
MAXIMUM OPERATING CONDITIONS
Maximum service pressure (tank full of water)
- Primary circuit: 3 bar
- Secondary circuit: 10 bar
Test pressure
(tank full of water)
- Primary circuit: 4.5 bar
- Secondary circuit: 13 bar
Operating temperature
- Maximum temperature: 90 °C
Water quality
• Chlorides: < 150 mg/l (Stainless steel 304)
< 2000 mg/l (Duplex)
• 6 ≤ ph ≤ 8
DIMENSIONS
TECHNICAL SPECIFICATION
FV/35 FV/50
A mm 1585 1830
B mm 390 390
C mm 200 200
D mm 542 542
E mm 125 125
F mm 645 645
G mm 80/80/125 100/100/150
H mm 1610 1880
I mm 800 800
Weight empty Kg 182 220