515756
52
Zoom out
Zoom in
Previous page
1/165
Next page
50
General Data - Heatpump (R22)
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
MWM 025GR MWM 030FR
MLC 025CR MLC 028CR
Btu/h 23,500 27000
W
6,890 7913
Btu/h
24,000 27000
W
7,030 7913
W
2,530 2778
W 2,450 2818
A 11.3 13.2
A 11.1 13.3
V/Ph/Hz
W/W
2.72 2.85
W/W
2.87 2.81
HIGH l/s / cfm 297 / 630 316 / 670
MEDIUM l/s / cfm 231 / 490 297 / 630
LOW l/s / cfm
208 / 440 236 / 500
dBA
49 / 44 / 42 49 / 47 / 45
HEIGHT mm/in
304 / 12.0 360 / 14.2
WIDTH mm/in
1062 / 41.8 1200 / 47.2
DEPTH mm/in 222 / 8.7 200 / 7.9
HEIGHT mm/in 378 / 14.9 420 / 16.5
WIDTH mm/in 1130 / 44.5 1267 / 49.9
DEPTH mm/in 292 / 11.5 260 / 10.2
kg/lb
16 / 35.27 17 / 37.48
mm/in
l/s / cfm
755 / 1600 632 / 1340
dBA
52 54
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb
62 / 136.7 68 / 149.9
FLARE VALVE FLARE VALVE
LIQUID mm/in
GAS mm/in
kg/lb 1.5 / 3.3 2.1 / 4.63
EER
COP
REFRIGERANT CONTROL (EXPANSION DEVICE)
OUTDOOR CAP. TUBE
UNIT DIMENSION
AIR FLOW
INDOOR UNIT
CONTROL
AIR DISCHARGE
OPERATION
UNIT DIMENSION
PACKING DIMENSION
AIR FLOW
SOUND PRESSURE LEVEL (H/M/L)
PACKING DIMENSION
OUTDOOR UNIT
UNIT WEIGHT
CONDENSATE DRAIN SIZE
SOUND PRESSURE LEVEL
UNIT WEIGHT
PIPE CONNECTION
TYPE
SIZE
REFRIGERANT CHARGE
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
LCD REMOTE CONTROL
20 / 0.79
750 / 29.5
MODEL
OUTDOOR UNIT
INDOOR UNIT
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE
415 / 16.3
9.52 / 3/8
15.88 / 5/8
220-240/1/50
R22
855 / 33.7
328 / 12.9
810 / 31.9
990 / 39.0
DOUBLE LOUVER (UP & DOWN) & GRILLE (LEFT & RIGHT)
AWM 25GR AWM 301R
ALC 25CR ALC 28CR
52


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Acson A5WM 09G-GR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Acson A5WM 09G-GR in the language / languages: English as an attachment in your email.

The manual is 17,38 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info