Installation and Service Manual Upsilon-Series
57
Block.
B000sc00
Error
E000sc00
Message
M000sc00
14 Errorreport
On the display, errors found are shown in the form of a message or blocking on a blue
screen or an error on a red screen.
- Blocking This is a temporary error that will sort itself out, or it will block the
boiler after several attempts (error)(Except: Bx01sc01 = reset)
- Error Error implies a blocking of the boiler and can only be solved by a
reset and/or intervention of a service engineer.
- Message Implies a message such as low water pressure, but the device will
remain operational.
Point of attention requiring short-term intervention.
The code consists of a Main Code and a Subcode
Main code Blocking = B
Main code Error = E
Main code Message = M
Followed by a character 0 = boiler
1 = burner A
2 = burner B
Subcode always starts with sc
Bx01sc01 Fan does not run on correct speed (Reset necessary). Fan defective.
Bx03sc01* Flow sensor T1 open
Bx03sc02* Flow temperature T1 too high
Bx03sc03* Flow sensor T1a open
Bx03sc04* Flow temperature T1a too high
Bx05sc01* Return sensor T2 open
Bx05sc02* Return temperature T2 too high
Bx08sc01* General purpose contact open
Bx12sc01* Water pressure sensor open
Bx12sc02* Water pressure sensor closed
Bx12sc03* Water pressure lower than 0.7bar. Top up
Bx12sc04* Water pressure too high. Decrease pressure
Bx12sc05* No pressure increase on pump start
Bx13sc01* DT between T1 and T2 too high
Bx15sc01* Communication error between controls
Ex01sc01* Fan does not run on correct speed. Fan defective.
Ex02sc01* No ame after 4 start attempts
Ex02sc02* Insufcient ionisation
Ex04sc01* Flow temperature T1 too high
Ex04sc02* Flow sensor T1 closed
Ex04sc03* Flow temperature T1a too high
Ex04sc04* Flow sensor T1a closed
Ex06sc01* Return temperature T2 too high
Ex06sc02* Return sensor T2 closed
Ex18sc01* Unwanted ame forming
Ex14sc01* DT not fast enough
Ex14sc02* DT between T1 and T2 > 35°C
M024sc01 DHW sensor T3 open (when P122=1)
M024sc02 DHW sensor T3 closed (when P122=1)
M024sc03 Outside sensor T4 open
M024sc04 Outside sensor T4 closed
M024sc05 Common ow sensor T10 open
M024sc06 Common ow sensor T10 closed
M024sc08 Bus communication: Possibly no bus communication cable connected
Mx24sc09 Temperature increase (Gradient) not fast enough after burner start
Mx24sc10 DT between T1 and T2 > 35°C when gas valve opened
* When this code is shown with an M instead of a B or E then a reset with the reset button is possible.
OpenThermerrormes-
sages
Thecodingofthetrans-
mittedErrorMessages
onaOpenThermcon-
trollerisdisplayedas
follows:
(E)EB(E=ErrorCode=
Bandboilernumber)
example:ErrorCode
Ex02SC02onboiler6
willappearas(0)26
57


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith Upsilon UB-70 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith Upsilon UB-70 in the language / languages: English as an attachment in your email.

The manual is 9,91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith Upsilon UB-70

A.O. Smith Upsilon UB-70 User Manual - English - 2 pages

A.O. Smith Upsilon UB-70 Additional guide - English, Dutch - 2 pages

A.O. Smith Upsilon UB-70 User Manual - Dutch - 2 pages

A.O. Smith Upsilon UB-70 Installation Guide - Dutch - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info