When all boilers have been electrically commissioned as described above, then the
heating system can be lled. Each boiler is tted with a lling and drain valve. The lling
hose from the water tap is then connected to it.
Filltheheatingsystemonlywithdrinkingwater.RefertotheWaterQualitychapter
forqualityrequirementsofthellingwater.
Waterpressure
Screen display
Good
Read-out
Operation
status
Technical
read-out
Description Action
FILLdd
00:00
FILL
Bx12sc03
xx.x°C
P0,0
Water pressure is 0 bar, boiler off Top up water
FILL
dd 00:00
FILL
Bx12sc03
xx.x°C
P>0,7
Water pressure above 0.7 bar. The boiler
is off. The automatic venting program
starts
Top up water until
approx. 1,7 bar
Block.
dd 00:00
Vent
Prog.
xx.x°C
P>1,2
Automatic venting program, afterwards
(approx. 13 min.) boiler is on standby
Top up water until
approx. 1,7 bar
Good
dd 00:00
(variable)
xx.x°C
P>1,0 <4,0
Water pressure is good. Boiler standby or
in normal operation
None
Block.
dd 00:00
xx.x°C
P>4,0
Water pressure too high, boiler off due to
blocking
Drain water until
approx. 1,7 bar
Good
dd 00:00
(variable)
xx.x°C
P<3,7
Water pressure is good. Boiler operates
normally again
None
Message/
Block.
dd 00:00
FILL
Message
Mx24sc14
xx.x°C
P<1 >0,7
Water pressure too low. Boiler is limited
to 50% load
Top up water until
approx. 1,7 bar
Ventingprogram
When, on lling the system, the water pressure rises above 0.7 bar, the venting program
will start automatically. The program lasts approx. 13 minutes and in doing so, turns
the pump on and off and, if tted, the three-way valve every 80 seconds to remove the
remaining air from the boiler. All venting points still have to be vented when lling the
installation. The boiler will be on standby after the venting program.
Theautomaticventingprogramonlyventstheboilerandnottherestoftheinstal-
lation.
Read-out 1 (Good status) displays Block. with actual day and time on the screen.
Read-out 2 (operational status) displays Vent Prog on the screen. [From Good press
the – button 1x: Vent Prog is now displayed]
Interrupting the venting program (not recommended) is only possible from the setting
level by pressing OK during the venting program.
For boiler checks please refer to the chapter Checks prior to commissioning.
For any checks or setting changes, refer to the Basic Settings chapter.
FILL
Block.
we 10:17
42


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith Upsilon UB-70 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith Upsilon UB-70 in the language / languages: English as an attachment in your email.

The manual is 9,91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith Upsilon UB-70

A.O. Smith Upsilon UB-70 User Manual - English - 2 pages

A.O. Smith Upsilon UB-70 Additional guide - English, Dutch - 2 pages

A.O. Smith Upsilon UB-70 User Manual - Dutch - 2 pages

A.O. Smith Upsilon UB-70 Installation Guide - Dutch - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info