Installation and Service Manual Upsilon-Series
34
3. 0-10Volt-control
At a heat demand of the 0-10 Volt controller a signal is sent out and varies from 0-10
Volt. This signal is translated by the Upsilon boiler to a set value (desired ow water
temperature or load) which is send via the data bus to the boiler(s). Depending on the
Voltage the set value becomes higher or lower.
The 0-10 Volt-controller must be connected to terminal 3, position 9 and 10.
The choice for temperature or load control can be done by a parameter setting.
Go to Setting level and Param. Chapter, than to Cascade Param. and select P101.
When P101 is adjusted to 1 the loadcontrol is set. On that moment P205 until P210 in
chapter Cascade Param. is released and can be adjusted according to specic requests.
When P101 is adjusted to 2 the temperaturecontrol is set. On that moment P215 until
P220 in chapter Cascade Param. is released and can be adjusted according to specic
requests.
See chapter 11 for the adjustment possibilities.
ADVICE:Choosefortemperaturecontrolforamorebalancedboilercontrol
Behaviourofconnectedexternalcontrols
- When using an OpenTherm or 0-10Volt control and a clock program is selected, the
clock program of the Upsilon will be ignored.
- When an on/off control is connected and the thermostat is switched on manually before
the pre-setted switch-on time, the clock programm will be ignored and will run on the
set day temperature. When swithing off manually the clock program will be followed.
0-10Volt
Open-
Therm
On/Off
T3
DHW
1 2 3 4 5 6 7 8 9 10 11 12 13 14
T10
General
purpose
LWCO
T4
Out
Figure 8.1.c
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith Upsilon UB-70 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith Upsilon UB-70 in the language / languages: English as an attachment in your email.

The manual is 9,91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith Upsilon UB-70

A.O. Smith Upsilon UB-70 User Manual - English - 2 pages

A.O. Smith Upsilon UB-70 Additional guide - English, Dutch - 2 pages

A.O. Smith Upsilon UB-70 User Manual - Dutch - 2 pages

A.O. Smith Upsilon UB-70 Installation Guide - Dutch - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info