671772
16
Zoom out
Zoom in
Previous page
1/68
Next page
Installation and Service Manual Upsilon-Series
16
6 Hydraulicandgaspipelinesystem
6.1 Heatingsystem
Install the CH-system in accordance with present legislation.
The pipe work headers are available in 2 dimensions, i.e. DN65 and DN100 and are
connected to one another by the ange couplings and gaskets, M12 or M16x55 bolts,
spring washers and nuts. The low velocity header and the complete installation can then
be connected to it.
Lowvelocityheader
There are 3 low velocity headers available:
0310335 Low velocity header for 1 or 2 XL boilers to max. 200kW (g. 6.1.a)
Boiler connections are 4x 1 1/2", installation connections are 2x 2". The low velocity
header must be suspended in the pipework. Supplied with automatic air vent, drain
valve and pocket for temperature sensor T10.
0310272 Low velocity headers DN65 to 452kW (g. 6.1.b)
0310273 Low velocity headers DN100 to 960kW
The low velocity headers comes standard with adjustable feet, automatic air vent,
drain valve, pocket for temperature sensor T10, M12 or M16x55 bolts, spring washers
and nuts. The low velocity header can be positioned on either the left or right hand
side of the pipe work headers.
0310290 Temperature sensor T3/T10 (g. 6.1.c)
Everysystemwith1ormoreUB-boilersmustbeprovidedwithaowtemperature
sensorT10andmustbeconnectedonthemasterboiler(address01)toterminal3,
position5and6.Theowsensormustbeplacedinthepocketofthelowvelocity
header.
Setofbends
The low velocity header can be positioned at a 90° angle. A set of bends may be used
for that purpose.
0310274 Bends set DN65 ow/return (g. 6.1.d)
0310275 Bends set DN100 ow/return
Blankinganges
The ends of the pipe work headers have to be tted with blanking anges. The blanking
anges come standard with a fully congured delivery, including bolts, spring washers
and gaskets.
0310276 Blanking ange set DN65 ow/return 2 items (g. 6.1.e)
0310277 Blanking ange set DN100 ow/return 2 items
Welded-onanges
Upon request, welded-on anges are available to connect CH-pipe lines to the secondary
side of the low velocity header and to connect the gas line.
0310336 Welded-on ange set DN65 ow/return 2 items + DN50 gas 1 item (g. 6.1.f)
0310337 Welded-on ange set DN100 ow/return 2 items + DN65 gas 1 item
Figure 6.1.b
Figure 6.1.d
Figure 6.1.e
Figure 6.1.f
Figure 6.1.c
Figure 6.1.a
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith Upsilon UB-140 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith Upsilon UB-140 in the language / languages: English as an attachment in your email.

The manual is 9,91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith Upsilon UB-140

A.O. Smith Upsilon UB-140 User Manual - English - 2 pages

A.O. Smith Upsilon UB-140 User Manual - English, Dutch - 2 pages

A.O. Smith Upsilon UB-140 User Manual - Dutch - 2 pages

A.O. Smith Upsilon UB-140 Installation Guide - Dutch - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info