5.4 Operating cycle
The water temperature (T
1
) at the top of the water heater is used to control when the gas
burner is started and stopped. The temperature changes in the water heater are used for
switching the solar heating system on and off (using T
1
and S
2
). T
1
is the curve shown in
the figure. The controller uses two measured values to calculate this temperature: T
1
(7)
and T
2
(13). In addition, temperatures S
1
, S
2
and S
3
are used by the solar heating system
controller. S
1
is measured in the solar collector. S
2
is located between the inlet and outlet
of the heat exchanger of the storage tank. S
3
is measured at the top of the storage tank.
Depending on whether or not hot water is being drawn off, hot water can be pumped from
the storage tank to the water heater. This happens if S
3
is 5 °C higher than T
top
(T
1
).
Water is then pumped from the water heater to the storage tank, causing hot water to
flow from the storage tank into the water heater. The pump switches off as soon as S
3
is
equal to T
1
.
The other settings that govern the control behaviour are:
T
set
T
set
is the the required water temperature that has been
set on the appliance (see
section 4.3.3.1)
. As soon as T
1
falls below T
set
, the solar heating system starts
heating the water, but only if the temperature of the heating fluid (S
1
) is greater
than the temperature measured at the appliance (sensor S
2
) by a given (adjustable)
amount. When T
1
= T
set
= T
solar limit
, heating by the solar heating system stops.
There is one exception to this rule, which is when T
solar limit
is set to a higher value
than T
set
.
Hysteresis
The moment that T
1
falls below (T
set
- T
solar diff
- hysteresis), the controller registers
such a heat demand that the gas burner and the solar heating system jointly heat
the water. The solar heating system is only employed when the temperature
measured by S
1
is a certain (adjustable) value grater than that of S
2
.
T
solar diff
When T
net
exceeds (T
set
- T
solar diff
), the gas burner is shut off and the water is
heated by the solar heating system alone. When T
1
rises above T
set
(provided that
T
set
= T
solar limit
), the solar heating system is switched off. The value of T
solar diff
is
adjustable (see section 9.2.8.4).
T
solar limit
Preset water temperature at which heating via the solar heating system is stopped
(see section 9.2.8.3)
.
Fig. Graphical representation of operating cycle
A.
Gas burner on
B.
Gas burner off
T1.
No heat demand, so water is not
heated
Water heated via solar heating system
Water heated via solar heating system
and gas burner
t.
time
T.
Temperature
45°C = Minimum tap water
temperature
0311753_SGS_28-120_II_UKUK_V2.0 , 2017-05-03 45
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith SGS 30 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith SGS 30 in the language / languages: English as an attachment in your email.

The manual is 5,92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith SGS 30

A.O. Smith SGS 30 User Manual - German - 128 pages

A.O. Smith SGS 30 Usermanual and installation guide - Dutch - 120 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info