5 - INSTALLATION
Figure 5-5 - Typical piping
means of appropriate siphon with disjunction capable
of preventing the pressurisation of the system and to
prevent the return of bad odours from the sewer (detail
“5” in gure 5-5).
because the condensate is acid some local codes
require the installation of a condensate neutraliser before
connection with the domestic waste drain (see section
9 for the value of acidity of the condensate and the ow
rate).
be connected to a plastic (not copper) drain pipe with a
minimum internal pipe diameter equal to or greater than
13 mm;
be installed in a way to prevent the liquid from freezing;
therefore pay attention to any external passings. It is
prohibited to drain into gutters or drainpipes;
to slope continuously towards the drain point, avoid high
points, which could pressurise the pipe;
5.8 - Safety pressure relief valve
The appliance is protected against overpressures by a
safety valve rated to 10 bar (see gures 3-1 and 3-4
detail “28”). The safety valve drain is conveyed on the same
pipe “9” as per gure 5-5.
CAUTION !!! If not connected to the drain,
whenever the safety valve should intervene, it could
cause damage to persons, animals or objects.
5.9 - Hydraulic and gas connections
CAUTION !!! The example in gure 5-5 is a
concept drawing only. It is up to the system designer
to determine the necessary components, including
additional equipment which in the judgement of the
designer are appropriate, in order to properly size,
congure and design that system and to ensure
compliance with local and national code.
Key of gure 5-5:
1 = Water heater
2 = Gas manual valve (EN 331 type-approved) (Field
supplied)
3 = Water isolation valve / Flow rate selector (Field
supplied)
4 = Water drain valve (Field supplied)
5 = Condensate drain (Field supplied)
6 = Gas inlet
7 = Cold water supply
8 = Domestic hot water
9 = Condensate drain pipe
10 = Water isolation valve (Field supplied)
11 = Filter (Field supplied)
5.10 - Secondary return
If distances between water heater and faucets/shower
heads are long then a recirculation system can be used to
get “instant” hot water.
When using an external recirculation pump make sure that
this is a specic hot water circulation pump.
The ow must exceed the minimum water ow.
Prevent for running the circulation pump 24/7 by using a
timer and/or thermostat or use an on-demand recirculation
system activated by push button or motion sensor.
To operate the secondary return pump properly, operate as
follow:
1.- install the appliance as shown in gure 4-4;
2.- open one tap of the sanitary utilities to eliminate
presence of air;
3.- turn off the secondary return pump;
4.- open one hot water sanitary tap and wait until the hot
water temperature is stable;
5.- close the hot water sanitary tap;
6.- check that after 50 seconds after closing the tap, tap
icon on the display has stopped ashing;
7.- if the tap icon keeps ashing, it means that the internal
pump can run the water in the secondary return circuit to a
value above 2 l/min (veriable on the parameter 1062);
8.- operate on the valve “A” of Figure 4-4 in order to bring
the recirculation ow rate to a value lower than 2 l/min;
9.- now the appliance can work correctly.
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith Instano ICW 25 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith Instano ICW 25 in the language / languages: English as an attachment in your email.

The manual is 9,27 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith Instano ICW 25

A.O. Smith Instano ICW 25 Usermanual and installation guide - Dutch - 64 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info