Indication Cause Measure
CO
2
value (at full load)
is not correct
The unit is not set for the correct gas
type
Make sure that the gas type corresponds
with the information on the rating plate
Make sure if the venturi restrictor has the
correct diameter, refer to Gas details (see
section 13.3).
Contaminated venturi Remove any contamination from the venturi
inlet.
Leakage between venturi and flexible
venturi connector
Make sure that the flexible venturi
connector is not damaged.
If necessary replace the flexible venturi
connector
Make sure that the flexible venturi
connector is correctly connected.
If necessary, tighten the clamp.
Recirculation of flue gases Make sure that the CO
2
-value measured
in the flue gas outlet is correct, refer to
CO
2
value (see section 8.9.4).
Make sure that the CO
2
value measured
in the air inlet is below 0.5 vol%.
If necessary, reconnect the venting
system and change the necessary seals.
12.1.2 Displayed errors
Note
For the coding of the connections, refer to the Electrical wiring diagram (see section
13.4).
Note
Contact your service and maintenance engineer if the error persists.
Code and description Cause Measure
C02 (lock out error)
Control error
Error message from the
controller
Incorrect reference voltage from the
AD converter.
EEPROM read error.
50 Hz error.
Internal communication error.
Gas control valve relay error.
Safety relay error.
Ignition relay error.
RAM error.
EEPROM error.
EEPROM content does not match the
software version.
Processor software error.
Ionisation circuit error
Make sure that the wiring/flame probe
are not damaged. If necessary, replace
the wiring/flame probe.
Make sure that the flame probe is not
bend. If necessary, replace the flame
probe.
Reset the controller.
If the error reappears, make sure that
the frequency of the power supply is 50
Hz (-1, +1 Hz).
If the frequency is not correct, contact
your service and maintenance engineer.
If the frequency is correct and the error
reapers, replace the controller.
Make sure that there is no "floating zero".
If necessary, install an isolating
transformer.
C03 (blocking error)
Control error
More then 7 resets detected in a short
period.
Wait for the error to disappear (maximal 1
hour).
If the error does not disappear, replace the
controller
C04 (blocking error)
Control error
This error appears when the controller
and/or display is replaced.
Incorrect selection of the water heater.
Turn the water heater OFF and ON. When
the error reappears contact your supplier.
n
0312266_INNOVO_UKUK_V3.0, 2017-02-10 73
73


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith Innovo IR 32-245 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith Innovo IR 32-245 in the language / languages: English as an attachment in your email.

The manual is 7 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith Innovo IR 32-245

A.O. Smith Innovo IR 32-245 Usermanual and installation guide - German - 92 pages

A.O. Smith Innovo IR 32-245 Usermanual and installation guide - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info