BMS Interface Module
35
6 Status
6.1
6.2
Via the BMS Interface, the state of the water heater and the solar control can be read out
separately. The actual state of the control of the water heater can be found on parameter 7.
When a solar control is present, its state can be viewed on parameter 22.
The numbers that will be read out refer to certain states of the control(s). Some states shall
appear and disappear so quickly that they won’t be visible. This is no problem.
In the table beneath, the reference to the numbers is specified:
Control water heater
Code Description
0 Resetting the control
1 Resetting the control
2 Standby, no active burner cycle
3 Pre purge of the fan / unit
4 Pre purge of the fan / unit
5 Pre purge of the fan / unit
6 Check safety devices
7 Check safety devices
8 Ignition of the gas mixture
9 Ignition of the gas mixture
10 Burning is started, unit is heating up
11 Stop signal for burner cycle
12 Stop signal for burner cycle
13 Post purge of the fan / unit
14 Post purge of the fan / unit
15 Error present
16 Error present
17 Internal check of the control
18 Internal check of the control
19 Internal check of the control
20 Internal check of the control
21 Waiting time between states
Solar control
Code Description
0 Resetting the solar control
1 Resetting the solar control
2 Standby, no active solar cycle
3 Solar pump started, unit is heating up
4 Error present
5 Waiting time between states
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith BMS interface voor BFC SGE en SGS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith BMS interface voor BFC SGE en SGS in the language / languages: Dutch as an attachment in your email.

The manual is 1,2 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info