Installation
30 Instruction manual BFC
3
is
Explanation of types of installation
Note
Make sure that the chimney flue discharges into an area approved for this
type of installation.
3.9.3 Concentric connections
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre towards
the water heater.
Flue gas discharge requirements for concentric systems (C13, C33)
Caution
Both conditions stated in the table must be fulfilled.
Even if you use less than the stated maximum number of bends, the maximum
pipe length still may not be exceeded.
Even if you use less than the stated maximum pipe length, the maximum
number of bends still may not be exceeded.
The following example illustrates how to use the table.
Practical example of concentric flue gas discharge
Example
The figure shows a BFC 30 installation. The water heater must be fitted with 25
m of concentric pipe (C13/C33) and four 90 degree bends. The configuration
must be checked for compliance with the requirements stated in the table.
Installation type Description
B23 Air for combustion is drawn from the boiler room.
C13 Concentric and/or parallel wall flue terminal.
C33 Concentric and / or parallel roof flue terminal
C43 Water heaters on common air supply and flue gas discharge (concentric
and/or parallel) in multi-storey building.
C53 Air supply and flue gas discharge terminal types mixed.
C63 Water heaters supplied without flue gas discharge materials and/or terminal.
These water heaters must be installed in compliance with local regulations.
Appliance Diameter Maximum
length
Maximum
number of
90
o
bends
BFC 28, 30, 50, 60 100/150 mm 40 m 7
BFC 80, 100, 120 130/200 mm 15 m 4
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith BFC60 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith BFC60 in the language / languages: English as an attachment in your email.

The manual is 3,04 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith BFC60

A.O. Smith BFC60 Usermanual and installation guide - German - 100 pages

A.O. Smith BFC60 User Manual - Dutch - 116 pages

A.O. Smith BFC60 Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info