503220
67
Zoom out
Zoom in
Previous page
1/100
Next page
Instruction manual BFC 67
is
12 Service program
12.1 Introduction
The service program is used by the installation
engineer or service and maintenance engineer for:
Displaying the water heater history;
Displaying the error history
;
Displaying the water heater history;
Display the selected water heater
;
Switching the pump on or off;
Setting the service interval
;
Service mode
;
Setting legionella prevention.
These sub-menus are briefly described in the
following paragraphs. If you are not generally familiar
with the use of the displays and menus, first read the
relevant chapter (7 "
The control panel").
Note
The notation convention for the service menu is
identical to that of the main menu (11.2 "
Notation
convention for menu-related instructions"). The
difference is, you use to bring up the service
program, instead of which brings up the main
menu.
12.2 Setting the hysteresis
If the preset temperature (SET POINT) is higher than
the current water temperature, the water heater might
not immediately start the operating cycle (9.3 "
The
appliance's heating cycle"). To prevent excessively
frequent switching on and off, there is a heating
margin. This margin is called the hysteresis. The
standard setting for this margin is 5°C. The operating
cycle starts when the water temperature drops to 5°C
below the SETPOINT and ends when the water
reaches 5°C above the SETPOINT.
Set the hysteresis as follows:
•:
HYSTERESIS UP
The figure shows an example
Set the hysteresis as follows
•:
HYSTERESIS DOWN
12.3 Displaying the error history
Display the error history as follows:
•:
ERROR HISTORY
The controller will display an overview of "Blocking
errors" and "Lock out errors". In both cases, note that
the controller reserves 15 lines for the last 15 error
messages. If there are fewer than 15 error messages,
an ellipsis (...) is displayed. The display first shows the
"Blocking errors". When is pressed, the
"Lock out errors" are then displayed.
The figure shows an example of "Blocking errors". In
this case, the text
ERROR HISTORY
is followed by
(B)
.
The figure shows an example of "Lock out errors". In
this case, the text
ERROR HISTORY
is followed by
(L)
.
Note
For an overview of all errors and the possible
causes, please refer to the relevant
chapter (13 "Errors").
12.4 Displaying the water heater history
The water heater history sub-menu is used to display
the burning hours, the number of ignitions, the number
of flame errors and the number of ignition errors.
SERVICE MENU
»HYSTERESIS
^ ERROR HISTORY
È APPLIANCE HISTORY
SELECT APPLIANCE
PUMP RELAY
SERVICE INTERVAL
SERVICE OPERATION
ANTI LEGIONELLA
HYSTERESIS UP »3ÉC
ERROR HISTORY(B)
S04 SENSOR ERROR
F06 IONIZATION
È CO2 50 HZ ERROR
ERROR HISTORY(L)
F02 FAN
F07 FLAME ERROR
È ...
67


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith BFC100 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith BFC100 in the language / languages: English as an attachment in your email.

The manual is 3,04 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of A.O. Smith BFC100

A.O. Smith BFC100 Usermanual and installation guide - German - 100 pages

A.O. Smith BFC100 User Manual - Dutch - 116 pages

A.O. Smith BFC100 Manual - Dutch - 2 pages


The manual is sent by email. Check your email